F-1500 Turbine Flow Meter Manual 02/18 - 1018-6 / 35726
Page 20
2.3.5 Insertion Procedure for Flow Meters with No Insertion Tool
1. Calculate the required sensor probe insertion length.
2. Fully retract the stem until the sensor head is touching the bottom of the stem housing.
Remove the two top stem clamp nuts and loosen two stem clamp bolts. Slide the stem
clamp away to expose the packing gland nuts. Loosen the two packing gland nuts.
3. Align the sensor head using the sensor alignment pointer. Adjust the alignment pointer
parallel to the pipe and pointing downstream.
4. Insert the sensor head into the pipe until insertion length, I, is achieved. Do not force the
stem into the pipe.
5. Tighten the packing gland nuts to stop leakage around the stem. Do not torque over 20 ft-lbs.
6. Slide the stem clamp back into position. Torque stem clamp bolts to 15 ft-lbs. Replace
the stem clamp nuts and torque to 10-15 ft-lbs.
CAUTION
The sensor alignment pointer must point downstream, in the direction of flow.
!
WARNING
The line pressure must be less than 50 psig for installation.
!
2.4
ADJUSTING THE DISPLAY ORIENTATION
Depending on installation requirements, you may need to rotate the position of the LCD
display / keypad. The orientation of the display / keypad may be changed in 90 degree
increments for easier viewing.
Figure 7. Display/Keypad Viewing Adjustment
The electronics boards are electrostatically sensitive. Wear a grounding wrist strap and make
sure to observe proper handling precautions required for static-sensitive components. To
adjust the display: