24
Section 2
2.
3 ID link
uni
t:
M
o
de
l V70
0
-L11
V700-L11
User's Manual
Section 2
Unit Specifications
■
General specifications
■
24 V power terminals/setup DIP-SW
Open the cover to access 24 V power terminals and setup DIP-SW.
• Recommended 24 V power supply: Model S82K-03024 (OMRON)
• Set the RS-485 terminator setting to ON for the link units on both ends of multidrop, and to OFF for
other units. If only one link unit is operated, set the terminator setting to ON.
Characteristic
Specification
Comment
Supply voltage
24 VDC,
+
10%,
−
15%
Supplied from the power terminals
Current consump-
tion
250 mA max.
Approx. 10 A max. with rush current
Dimensions
110
×
65
×
64 mm
Except for mounting hook
Protection rating
(IEC 60529)
IP20
Operating ambient
temperature
0 to
+
40
°
C
No freezing
Operating ambient
humidity
35 to 85%RH
No dew condensation
Storage ambient
temperature
−
15 to
+
50
°
C
No freezing
Storage ambient
humidity
35 to 85%RH
No dew condensation
Mounting system
Secured with two M4 screws.
Wrong wiring connection can lead to a malfunction of the equipment. Be fully sure of the correct
wiring connections.
24 VDC
6 mm max.
6 mm max.
1
ON
2
3
4
5
6
7
8
9
10
SW
No.
Description
Meaning
(Content within a box represents factory-setting)
1
Node No. 1
01 to 31
No. 1 is LSB, and No. 5 is MSB.
(For correspondence between DIP-SW settings
and node Nos., see the table in the next page.)
2
Node No. 2
3
Node No. 3
4
Node No. 4
5
Node No. 5
6
Baud rate setting 1
38400/ 9200/ 9600 /4800bps
[ON,ON] [ON,OFF] [OFF,OFF] [OFF,ON]
:[No7,No6]
7
Baud rate setting 2
8
Reserved
Always leave in OFF position.
9
Reserved
Always leave in OFF position.
10
RS-485 terminator
ON/ OFF
• For wiring connections, use
compression rings.
• Use the M3 compression
rings illustrated below.