Installation orienta-
tion and restrictions
Installation orientation:
•
Connected to a CPU Unit
Possible in upright installation.
•
Connected to a Communications Coupler Unit
Possible in upright installation.
Restrictions: No restrictions
Terminal connection
diagram
24 VDC
A1
B1
A8
B8
IOV
IOG
IOV
IOG
IOV
IOG
IOV
IOG
A1
B1 C1
D1
A8
B8 C8
D8
IN1
IN2
IN3
IN4
NC
NC
NC
NC
SHT1+
SHT2+
SHT3+
SHT4+
IOV2
IOG2 SHT2- Input2-
IOV1
IOG1 SHT1- Input1-
IOV3
IOG3 SHT3- Input3-
IOV4
IOG4 SHT4- Input4-
Additional I/O Power
Supply Unit*3
Use a two-conductor
shielded twisted-pair
cable. Do not ground
the shield.
To use current input,
connect SHT□+ and
SHT□- with a
short-circuit cable.*4
High-speed Analog Input Unit
NX-HAD402
Two-wire sensor
Three-wire sensor
Output device
Input+
Input-
Input disconnection
•
When the input range is 1 to 5 V or 4 to 20 mA: Supported
•
Other input range: Not supported
*1.
This is the minimum value. The Units perform conversion in the sampling period determined based on the Number of
Samplings Setting. The sampling period must be set to this value or longer.
*2.
The following Unit cannot be connected next to the Unit.
•
Relay Output Unit (NX-OC
££££
)
*3.
Besides the Additional I/O Power Supply Unit, there are Units that can supply I/O power to the NX bus. For example,
you can use a Connected Communications Coupler Unit. If you use this Unit to supply I/O power to the High-speed
Analog Input Units, the Additional I/O Power Supply Unit is unnecessary. The Additional I/O Power Supply Unit is also
unnecessary if you do not use the trigger inputs of the High-speed Analog Input Units.
*4.
Short-circuit cables are not included in the product. The cable length must be 4 cm or less and allow for wiring to the
screwless clamping terminal block. Be sure to use cables and ferrules that are applicable to the screwless clamping
terminal block.
If the cable is too long, the analog input values may not be accurate.
*5.
To use this function, set the Disconnection Detection Enable/Disable to Enable.
Appendices
A - 10
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
Содержание Sysmac NX-series
Страница 4: ...Introduction 2 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 42: ...Sections in this Manual 40 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 100: ...4 Installation and Wiring 4 32 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 142: ...7 I O Data and List of Settings 7 24 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 238: ...10 Inspection and Maintenance 10 6 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 300: ...Appendices A 62 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 301: ...I Index I 1 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 303: ...W Wiring Terminal 4 7 Index I 3 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 304: ......
Страница 305: ......