Power Supply Design
• Use all Units within the I/O power supply ranges that are given in the specifications.
• The I/O power supply current for the CPU Rack with an NX-series CPU Unit should be within the
range specified for the CPU Unit model. For example, use the NX1P2 CPU Unit with a current of 4 A
or less. Using the currents that are outside of the specifications may cause failure or corruption. Re-
fer to the user’s manual for the connected CPU Unit for the I/O power supply current for the CPU
Unit model.
• Supply sufficient power according to the contents of this manual.
• Use the power supply voltage that is specified in this manual.
• Do not apply voltages that exceed the rated value to any Input Unit.
• Do not apply voltages or connect loads to the Output Units or slaves in excess of the maximum rat-
ings.
• Inrush current occurs when the power supply is turned ON. When selecting fuses or breakers for
external circuits, consider their fusing and detection characteristics as well as the above precautions
and allow sufficient margin in shut-off performance.
• Install external breakers and take other safety measures against short-circuiting and overcurrents in
external wiring.
Turning ON the Power Supply
• When you set the Operating Mode at Startup, confirm that no adverse effect will occur in the sys-
tem.
Actual Operation
• Before you start operation, always register the NX Units that are connected to the Communications
Coupler Unit in the host communications master as the Unit Configuration Information.
• Check the user program, data, and parameter settings for proper execution before you use them for
actual operation.
• If you change the fail-soft operation setting, the output status when the error occurs may also
change. Confirm safety before you change the fail-soft operation setting.
• If you use fail-soft operation, write programming to determine whether Unit I/O data is valid. Without
such programming, the user program cannot distinguish between Units for which I/O refreshing is
continued and Units for which I/O refreshing is stopped.
Turning OFF the Power Supply
• Do not disconnect the cable or turn OFF the power supply to the Controller or a Slave Terminal
when downloading data or the user program from the Support Software.
• Always turn OFF the external power supply to the Units before attempting any of the following.
a) Mounting or removing an NX Unit, Communications Coupler Unit, CPU Unit, Industrial PC, or
Communication Control Unit
b) Assembling Units
c) Setting DIP switches or rotary switches
d) Connecting or wiring cables
Precautions for Safe Use
21
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
Содержание Sysmac NX-series
Страница 4: ...Introduction 2 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 42: ...Sections in this Manual 40 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 100: ...4 Installation and Wiring 4 32 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 142: ...7 I O Data and List of Settings 7 24 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 238: ...10 Inspection and Maintenance 10 6 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 300: ...Appendices A 62 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 301: ...I Index I 1 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 303: ...W Wiring Terminal 4 7 Index I 3 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 304: ......
Страница 305: ......