Bit
Data name
Data
type
I/O port name
1
Ch
£
Moving
Average Filter 1
Disable
1: Disables the moving average filter 1.
0: Enables the moving average filter 1.
If the Filter 1 Moving Average Count is set to 0 in the
Unit operation settings, the moving average filter 1 will
not be enabled even if you set this bit to 0.
BOOL
Ch
£
Moving
Average Filter 1
Disable
2
Ch
£
Moving
Average Filter 2
Disable
1: Disables the moving average filter 2.
0: Enables the moving average filter 2.
If the Filter 2 Moving Average Count is set to 0 in the
Unit operation settings, the moving average filter 2 will
not be enabled even if you set this bit to 0.
BOOL
Ch
£
Moving
Average Filter 2
Disable
3
Ch
£
Zero Set
Execution
0→1: Executes the zero set.
1→0: Executes the zero reset.
BOOL
Ch
£
Zero Set
Execution
4 to
15
Ch
£
Reserved
---
---
---
*1.
1 is TRUE and 0 is FALSE.
Precautions for Correct Use
Do not access reserved data. Doing so may cause unintended operation if some function is as-
signed to the reserved data in an upgrade.
7-1-3
Precautions for the I/O Data Size
The input data size of the High-speed Analog Input Unit will increase as the set value for
Ch
£
Number of Samplings Setting
increases. For example, when all the channels are enabled, and the
number of samplings for each channel is set to 10, 50, 100, and 200, the input data size is as follows.
The table shows that the input data size increases as the number of samplings increases.
Number of samplings for each channel Input data size
10 times
136 bytes
50 times
456 bytes
100 times
856 bytes
200 times
1,656 bytes
At this time, you should consider the restrictions given in the table below.
Item
Description
Size of NX Unit I/O data
that can be allocated to the
CPU Unit or Communica-
tions Coupler Unit
There are restrictions on the size of NX Unit I/O data that can be allocated to the
CPU or Communications Coupler Unit connected to a High-speed Analog Input
For example, the size of I/O data for an NX102 CPU Unit will be restricted
as below:
•
Input: 8,192 bytes
•
Output: 8,192 bytes
Refer to the user’s manual for the connected CPU Unit or Communications Cou-
pler Unit for restriction on the allocatable I/O data size for the CPU Unit or Com-
munications Coupler Unit.
7 I/O Data and List of Settings
7 - 12
NX-series Analog I/O Units User’s Manual for High-speed Analog Input Units (W592)
Содержание Sysmac NX-series
Страница 4: ...Introduction 2 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 42: ...Sections in this Manual 40 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 100: ...4 Installation and Wiring 4 32 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 142: ...7 I O Data and List of Settings 7 24 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 238: ...10 Inspection and Maintenance 10 6 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 300: ...Appendices A 62 NX series Analog I O Units User s Manual for High speed Analog Input Units W592...
Страница 301: ...I Index I 1 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 303: ...W Wiring Terminal 4 7 Index I 3 NX series Analog I O Units User s Manual for High speed Analog Input Units W592 I...
Страница 304: ......
Страница 305: ......