5-5
5-2 Troubleshooting
5
Mai
n
tena
nce Oper
ations
5-2 Troubleshooting
Situation
Possible cause
Remedy
The motor
doesn't
work.
No voltage
observed for
Inverter outputs
U/T1, V/T2, and
W/T3.
• Is the A001 setting (frequency
reference selection) correct?
• Is the A002 setting (RUN command
selection) correct?
• Check the A001 setting.
• Check the A002 setting.
• Is the [485/OPE] communications
selector status correct?
• Is the [TM/PRG] selector status
correct?
• Check the [485/OPE]
communications selector.
• Check the [TM/PRG] selector.
• Is power supplied to terminals R/L1,
S/L2, and T/L3? If so, the POWER
LED indicator should light up.
• Check the connections of terminals
R/L1, S/L2, T/L3 and U/T1, V/T2,
W/T3.
• Turn on the power.
• Does the display show "E **"?
• Press the Mode key to check the
situation, and then reset.
• Is the allocation of the multi-function
input correct?
• Is the RUN key (RUN command)
turned on?
• Are FW (or RV) input and terminal SC
or PSC connected?
• Is the [SK/SR] selector status correct?
• Check the terminal allocation:
C001 to C006
• Turn on the RUN key (RUN
command).
• Connect FW (or RV) input to terminal
SC or PSC.
• Check the [SK/SR] selector.
• Is the frequency set with F001
selected?
• Is the potentiometer connected to
terminals FS/FV/FC?
• Press the key to set.
• If terminal mode is selected, set the
potentiometer to FS/FV/FC.
• Are RS and FRS inputs still turned
on?
• Turn off these inputs.
Voltage
observed for
Inverter outputs
U/T1, V/T2, and
W/T3.
• Is the motor restrained?
• Or is it overloaded?
• Release the restraint and reduce the
load.
• Operate the motor separately.
Motor
rotation is
in reverse.
• Are output terminals U/T1, V/T2, and
W/T3 correct?
• Is the phase sequence of the motor U/
T1, V/T2, W/T3, and is the rotation in
forward or reverse?
• Connect according to the motor
phase sequence. (Generally, U/T1,
V/T2, W/T3 in forward)
• Is the control circuit terminal correct?
• Is F004 set correctly in the motor
rotation direction selection via the
Digital Operator?
• Select FW for forward and RV for
reverse.
Содержание SYSDRIVE 3G3MX-A2002
Страница 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Страница 24: ......
Страница 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Страница 90: ......
Страница 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Страница 180: ......
Страница 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Страница 188: ......
Страница 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Страница 205: ...7 8 7 4 Dimensional Drawing 7 Specifications 7 4 Dimensional Drawing 3G3MX A2002 AE002 120 110 67 5 6 5 103 2 6 7 80...
Страница 208: ...7 11 7 4 Dimensional Drawing 7 Specifications 3G3MX A4004 AE007 139 2 6 7 98 118 4 130 2 5 110 5...
Страница 210: ...7 13 7 4 Dimensional Drawing 7 Specifications 3G3MX A2055 A2075 A4055 A4075 205 220 6 5 6 164 180 2 6 7 155 5 5...
Страница 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Страница 223: ...7 26 7 5 Options 7 Specifications 3G3AX EFI25 L3 T S R L1 L2 10 2 260 MIN 205 235 308 5 331 355 160 40 60 164 182...
Страница 230: ......
Страница 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Страница 249: ...INDEX...
Страница 252: ......