4-20
4-2 Function Mode
4
Func
tions
D Operation
• Operation where the control volume is proportional to the variation ratio of the target value
• PI operation is the combination of the above P and I operations; PD is P and D operations; PID is
P, I and D operations.
PID Gain Adjustment
• If a stable response cannot be obtained in PID function operation, adjust each gain as follows
according to the situation.
• Feedback value variation is slow when the target value is changed.
→
Raise P gain.
• The feedback value changes fast but isn't stable.
→
Lower P gain.
• The target and feedback values wouldn't match smoothly.
→
Lower I gain.
• The feedback value fluctuates unstably.
→
Raise I gain.
• Response is slow even with P gain raised.
→
Raise D gain.
• With P gain raised, the feedback value fluctuates and isn't stable.
→
Lower D gain.
Excessive Deviation/Output
• You can set PID deviation excessive level C044 during PID control. If the PID deviation reaches
the PID deviation excessive level (C044), the multi-function output terminal is turned on.
• C044 can be set from 0 to 100. The setting corresponds to the range of 0 to the maximum target
value.
• Allocate 04 (OD) to any of multi-function output terminals P1 and P2 (C021 and C022) or relay
output terminals MA and MB (C026).
PID Feedback Value Monitor
• You can monitor the PID feedback value with d004.
• The monitor value is displayed as the multiplied value of the PID scale (A075).
"Monitor display" = "Feedback value (%)" × "A075 setting"
PID Integral Reset
• Clears the integral value of PID operation.
• Allocate 24 (PIDC) to the desired multi-function input.
• Clears the integral value every time the PIDC terminal is turned on.
Do not turn on the PIDC terminal during PID operation to avoid an overcurrent trip.
Turn on the PIDC terminal after turning off PID operation.
The integral value is cleared during free running or retry.
Large
Small
Target
value
Control
volume
A074
Large
Small
A074
Содержание SYSDRIVE 3G3MX-A2002
Страница 1: ...Cat No I559 E1 01 USER S MANUAL SYSDRIVE MXSERIES Multi function Compact Inverter...
Страница 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 3...
Страница 24: ......
Страница 25: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Removing and Mounting Each Part 2 5 2 3 Wiring 2 10...
Страница 90: ......
Страница 91: ...Chapter 4 Functions 4 1 Monitor Mode 4 1 4 2 Function Mode 4 5...
Страница 180: ......
Страница 181: ...Chapter 5 Maintenance Operations 5 1 Special Display List 5 1 5 2 Troubleshooting 5 5...
Страница 188: ......
Страница 189: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 6 2 Storage 6 7...
Страница 205: ...7 8 7 4 Dimensional Drawing 7 Specifications 7 4 Dimensional Drawing 3G3MX A2002 AE002 120 110 67 5 6 5 103 2 6 7 80...
Страница 208: ...7 11 7 4 Dimensional Drawing 7 Specifications 3G3MX A4004 AE007 139 2 6 7 98 118 4 130 2 5 110 5...
Страница 210: ...7 13 7 4 Dimensional Drawing 7 Specifications 3G3MX A2055 A2075 A4055 A4075 205 220 6 5 6 164 180 2 6 7 155 5 5...
Страница 212: ...7 15 7 5 Options 7 Specifications 3G3AX RBU41 95 75 2 5 208 218 5 145 35 100 5...
Страница 223: ...7 26 7 5 Options 7 Specifications 3G3AX EFI25 L3 T S R L1 L2 10 2 260 MIN 205 235 308 5 331 355 160 40 60 164 182...
Страница 230: ......
Страница 231: ...Appendix Appendix 1 Parameter List App 1 Appendix 2 Product Life Curve App 17...
Страница 249: ...INDEX...
Страница 252: ......