Closed-Loop Connectors
Wire range
Terminal
Closed-loop connectors
AWG
mm
2
screw
22
0.5
M3.5, M4
1.25 to 3.5, 1.25 to 4
18
0.75
16
1.25
14
2
M4
2 to 4
M5
2 to 5
12
3.5
M4
3.5 to 4
M5
3.5 to 5
10
5.5
M4
5.5 to 4
M5
5.5 to 5
8
8
M5
8 to 5
M6
8 to 6
6
14
M6
14 to 6
4
22
M6
22 to 8
3
30
M8
30 to 8
2
38
M8
38 to 8
2
38
M10
38 to 10
1
50
M8
50 to 8
1/0
60
M10
60 to 10
2-5
Control Circuit
The external interconnection wiring must be performed with following proce-
dures.
After completing SYSDRIVE 3G3IV interconnections, be sure to check that
connections are correct. Never use control circuit buzzer check.
(1) Separation of control circuit leads and main circuit leads:
Signal leads 1 through 20 must be separated from main circuit leads L1 (R),
L2 (S), L3 (T), B1/(+), B2, (--), B0/(--), T1 (U), T2 (V), T3 (W), and other power
cables to prevent erroneous operation caused by noise interference.
(2) Control circuit leads 9 10 18 19 20 (contact output) must be separated
from leads 1 to 8, 21 22 25 26 27 and 11 to 17.
Use the twisted shielded or twisted-pair shielded lead for the control circuit
line and connect the shield sheath to the inverter terminal 12 (G). See Fig. 3.
Fig. 3 Shielded Lead Termination
SHIELD
SHEATH
ARMOR
Never connect
Insulate these parts
with insulating tape.
TO INVERTER SHIELD
SHEATH TERMINAL 12 (G)
Section 2-5
Содержание SYSDRIVE 3G3IV
Страница 3: ...0 1 2 3 2 4 2 5 4 67 1 5 5 0 8 2 2 4 8 3 9 2 6 0 8 5...
Страница 4: ...0 33 3 0 3 3 0 33 3 3 0 33 3 0 3 3 0 3 0 3 4 5 1 3 5 4 0 33 0 5 5 0 5 5 3 6 2...
Страница 6: ...1 9 2 6 0 A 1 5 2...
Страница 9: ...1 9 2 6 0 0 1...
Страница 22: ...1 9 2 6 0 2 3 2 4 2 5 4 67 1 5 5 0...
Страница 29: ...1 9 2 6 0 A 1 8 2 2 4 8 3...
Страница 33: ...1 8 9 2 6 0 9 2 6 0 8 5...
Страница 38: ...A 9 2 6 0 0 33 3 0 3 3 0 33 3 3 0 33 3 0 3 3 0 3 0 3 4 5 1 3 5 4 0 33 0 5 5 0 5 5 3...