Omron Sti G9SX-SM032 Series Скачать руководство пользователя страница 2

(1) Use G9SX-SM

 within an enclosure with IP54 protection or higher 

according to IEC/EN60529. Be sure to connect the enclosure to earth(PE).

(2) Incorrect wiring may lead to loss of safety function. Wire conductors 

correctly and verify the operation of G9SX-SM

 before using the system 

in which G9SX-SM

 is incorporated. 

(3) Do not apply DC voltages exceeding the rated voltages, nor any AC 

voltages to G9SX-SM

. Do not connect to DC distribution network.

(4) Use DC supply satisfying requirements below to prevent electric shock.

- DC power supply with double or reinforced insulation, for example,  

according to IEC/EN60950 or EN50178 or a transformer according to 
IEC/EN61558.

- DC supply satisfies the requirement for class 2 circuits or limited 

voltage/current circuit stated in UL 508.

(5) Apply properly specified voltages to G9SX-SM

 inputs.

Applying inappropriate voltages cause G9SX-SM

 to fail to perform its 

specified function, which leads to the loss of safety functions or damages 
to G9SX-SM

.

(6) Auxiliary error outputs and auxiliary monitoring outputs are NOT safety 

outputs.
Do not use auxiliary outputs as any safety output.
Such incorrect use causes loss of safety function of G9SX-SM

 and its 

relevant system.

(7) After installation of G9SX-SM

, qualified personnel should confirm the 

installation, and should conduct test operations and maintenance.
The qualified personnel should be qualified and authorized to secure the 
safety on each phases of design, installation, running, maintenance and 
disposal of system.

(8) A person in charge, who is familiar to the machine in which G9SX-SM

 is 

to be installed, should conduct and verify the installation.

(9) G9SX-SM

 determines that motor stops when the standstill detection 

input voltage is predetermined value or less. According to the 
characteristic or load condition of motor, it may turn on safety detection 
outputs before motor stops completely. In that case, before operation, the 
qualified personnel should verify that risk of the rotation condition after 
output is acceptable.

(10) Perform daily and 6-month inspections for the G9SX-SM

. Otherwise, 

the system may fail to work properly, resulting in serious injury.

(11) Do not dismantle, repair, or modify G9SX-SM

. It may lead to loss of its 

safety functions.

(12) Use only appropriate components or devices complying with relevant 

safety standards corresponding to the required level of safety categories.
Conformity to requirements of safety category is determined as an entire 
system. 
It is recommended to consult a certification body regarding assessment 
of conformity to the required safety level.

(13) OMRON shall not be responsible for conformity with any safety 

standards regarding to customer's entire system.

(14) Disconnect G9SX-SM

 from power supply when wiring. Devices 

connected to G9SX-SM

 may operate unexpectedly.

(15) Be cautious not to have your fingers caught when attaching terminal 

sockets to the plugs on G9SX-SM

.

(16) Do not use in combustible gases or explosive gases.

(17) Driving voltage of the motor is impressed to the standstill detection 

inputs.  Connect  overcurrent protective equipment; fuse, circuit-breaker 
etc., (3A Max.) and tighten the wirings by rated tightening torque to the 
standstill detection inputs.

Precautions for Safe Use

(4) Following spacing around G9SX should be available to apply rated 

current to outputs of G9SX and for enough ventilation and wiring:

1) At least 25 mm beside side faces of G9SX.
2) At least 50 mm above top face of G9SX and below bottom face 

of G9SX.

(5) Wiring

1) For model G9SX-SM

Use the following to wire to G9SX-SM

.

-Solid wire: 0.2 to 2.5mm

2

  AWG24 to AWG12

-Stranded wire (Flexible wire): 0.2 to 2.5mm

2

  AWG24 to AWG12

Strip the cover of wire no longer than 7mm.

2) For model G9SX-SM

-RT (with screw terminals)

Tighten each screw with a specified torque of 0.5 to 0.6N

m, or 

the G9SX-SM

 may malfunction or generate heat.

(6) Use cables with length less than 100m to connect to standstill 

detection Inputs and EDM input respectively.

(7) 

Driving voltage of the motor is impressed to the standstill detection 

input and there is a possibility that a high level of noise is 
superimposed. The line of the standstill input must be separately 
installed from other signal lines.

(8) 

Set the time duration of Standstill detection time to an appropriate 

value that does not cause the loss of safety function of system.

(9) 

Tuning mode in User configuration is only for adjusting the Standstill 

determining time. In Tuning mode, auxiliary monitor output is enable 
however Safety Standstill detection outputs are not enabled. After 
the tuning is complete, be sure to change from Tuning mode to 
Monitoring mode for actual operation.

(10) 

Safety standstill detection outputs are only for controlling a  guard 

lock safety-door switch with mechanical lock.  They can not be 
used as safety outputs to drive contactors, or to control a guard 
lock safety-door switch with solenoid lock.

(11) To determine safety distance to hazards, take into account the 

delay of safety standstill detection outputs caused by the response 
time.

(12) Start entire system after more than 5s have passed since applying 

supply voltage to all G9SXs in the system.

(13) G9SX-SM

 may malfunction due to electro-magnetic disturbances.

Be sure to connect the terminal A2 to ground.

(14) This is a class A product. In residential areas it may cause radio 

interference, in which case the user may be required to take 
adequate measures to reduce interference.

(15) Devices connected to G9SX-SM

 may operate unexpectedly.

When replacing G9SX-SM

, disconnect it from power supply.

(16) Adhesion of solvent such as alcohol, thinner, trichloroethane or 

gasoline on the product should be avoided. Such solvents make 
the marking on G9SX-SM

 illegible and cause deterioration of 

parts.

(17) Connectable motor

AC induction motors can be connected to the G9SX-SM

. Servo 

motors cannot be connected.
When a motor with AC240V or more is used,connect neutral point 
of the power supply to earth.

(18) G9SX-SM

 does not have motor fault detective function or motor 

protective function. For motor protection, use designated external 
protective devices.

(19) For use with inverter

The dynamic break setting time should be set to 30 seconds or 
shorter.  Otherwise, the G9SX-SM

 may detect a disconnect fault 

of the wiring.
Also in the following cases, the standstill detection function may 
not properly work even while the motor is in standstill.
1. An inverter with a large output residual voltage is used, and the 

contactor connected in serial with the inverter is in the ON state.

2. The inverter is  executing the auto tuning function.

(20) Operate the reset input more than 0.4 seconds immediately after 

the safety outputs are OFF.
G9SX-SM

 does not accept the reset input from when the 

outputs are turned ON and until 0.4 seconds passes after the 
outputs are turned OFF.

Precautions for Correct Use

(1) Handle with care

Do not drop G9SX-SM

 to the ground or expose to excessive 

vibration or mechanical shocks. G9SX-SM

 may be damaged and 

may not function properly.

(2) Conditions of storage and usage

Do not store or use in such conditions stated below.

1) In direct sunlight
2) At ambient temperatures out of the range of -10 to 55 

°

C

3) At relative humidity out of the range of 25% to 85% or under 

such temperature change that causes condensation.

4) In corrosive or combustible gases
5) With vibration or mechanical shocks out of the rated values.
6) Under splashing of water, oil, chemicals
7) In the atmosphere containing dust, saline or metal powder.

G9SX-SM

 may be damaged and may not function properly.

(3) Mounting

Mount G9SX to DIN rails with attachments (TYPE PFP-M, not 
incorporated to this product), not to drop out of rails by vibration etc. 
especially when the length of DIN railing is short compared to the 
widths of G9SX.
Do not use G9SX-SM

 at altitudes over 1,000 meters.

- 2 -

25mm min

25mm min

50mm min

50mm min

G9SX-NS202
24VDC

G9SX-SM032
24VDC

No.

AND

NS

FB

ERR

EI

PWB

D4

L1

S24

S14

A2

X2

T42

T41

A1

X1

D2

D1

D3

T32 T33

T31

No.

OFF-DELAY

0.5

0.4

0.3

0.2

3.0

2.5

2.0

1.8

1.4

1.2

1.0

0.9

0.8

0.6

0.7

0

L1

S54

S44

S24

S14

D4

A2

T42

T41

T22

T21

A1

X2

X1

D3

D2

D1

Y1

T12

T11

T33

T31

T1

ERR

EI

AND

FB

ED

T2

NS

PWR

T32

G9SX-NSA222-T03
24VDC

PWR

EDM

CH1

CH2

ES

ERR

SET

Содержание Sti G9SX-SM032 Series

Страница 1: ...ments Use approved devices with forcibly guided contacts complying with IEC 61810 3 EN 50205 For feedback purpose use devices with contacts capable of switching micro loads of 24VDC 5mA Guard Lock Safety door Switch Use approved devices complying with IEC EN 60947 4 1 auxiliary contact linked with power contact mirror contact For feedback purpose use devices with contacts capable of switching micr...

Страница 2: ...s impressed to the standstill detection input and there is a possibility that a high level of noise is superimposed The line of the standstill input must be separately installed from other signal lines 8 Set the time duration of Standstill detection time to an appropriate value that does not cause the loss of safety function of system 9 Tuning mode in User configuration is only for adjusting the S...

Страница 3: ...ue can be applied to the Monitoring Mode without having to use the Tuning Mode Functions 1 Use the Operation Preset switch on the back side to select either Standard Configuration or User Configuration The selected configuration mode is enabled at power on Normally please use Standard Configuration which is set as factory default If the Standstill determining time is found too long in the Standard...

Страница 4: ...urns on 2 Preset Switches Name Function State Value position of switch Configuration Preset Switch Selects either Standard configuration or User configuration STD Standard configuration default setting USR User configuration Mode Preset Switch Selects either Tuning mode or Monitoring mode in User configuration 3 MON Monitoring mode default setting TUN Tuning mode Standstill determining time Preset...

Страница 5: ... Auxiliary outputs control ES1 T31 T32 1 Internal power supply circuit is not isolated 2 Standstill detection inputs are isolated respectively 3 The Safety standstill detection outputs ES1 ES3 are internally redundant respectively 2 2 6 6 100 max 115 max 35 5 max 35 1 Dimensions 4 Type G9SX SM032 Note 1 Above outline drawing is for RC terminal type 1 Typical dimension 2 For RC terminal type only ...

Страница 6: ... together and DIN rail Between standstill detection inputs Z1 Z2 Z3 Z4 Between Standstill detection input terminals connected together and Power supply input terminals and other input and output terminals connected together Between Standstill detection input terminals connected together and DIN rail Between all terminals without Standstill detection input terminals connected together and DIN rail ...

Страница 7: ...age Standstill detection input 2 voltage Lock release switch S5 S1 KM1 KM2 M Guard lock Safety door Switch S2 Safety Limit Switch S3 Stop signal S4 Reset Switch S5 Lock release switch Contactor 3 phase motor Devices Motor rotation Guard open close Guard close open able to open the guard S4 S2 Note1 This example is corresponding to category 4 Stop category 1 Refer to 7 Safety Category EN ISO13849 1...

Страница 8: ...ety door Switch S2 Safety limit switch S3 Stop signal S4 Reset switch S5 Lock release switch Contactor KM3 KM4 Contactor for star delta starter 3 phase motor Devices Motor rotation G9SX SM032 DC24V 3 phase motor with Star Delta wiring G9SX BC202 DC24V Guard lock Safety door switch Safety limit switch 2ch input manual reset S1 Guard lock Safety door Switch S4 Guard open close Guard close open able ...

Страница 9: ...rotation is detected in this system with a guard open Its response time is an accumulation of G9SX SM and G9SX GS Determine a safety distance to hazards in view of this response time Timing chart Emergency stop S1 Guard lock Safety door switch S3 Reset switch S2 Logical AND connection input T41 Reset switch S5 Safety limit switch S4 KM1 KM2 NC contact KM1 KM2 NO contact Inverter operation signal f...

Страница 10: ... minus to the A2 terminal Wiring of inputs and outputs T31 T32 EDM input KM T31 T32 To turn on Safety standstill detection outputs ON state signals should be input to T32 Otherwise Safety standstill detection outputs will not be turned ON Turns ON OFF according to the state of standstill detection inputs and EDM input Outputs a signal of the same logic as Safety standstill detection outputs Connec...

Страница 11: ...etection time preset switches 2 Replace with a new product 1 Check the supply voltage to G9SX units Fault by electro magnetic disturbance or of internal circuits 1 Excessive electro magnetic disturbance 2 Failures of the parts of internal circuits Faults involved with Standstill detection input 1 Faults involved with Standstill detection input 2 Faults involved with Standstill detection input Faul...

Отзывы: