Setup steps
1
The Web page of [UPS management]-[shutdown] on the master uninterruptible
power supply (UPS) side is accessed, and a shutdown is set up according to the
2
The Web page of [UPS management]-[UPS remote shutdown] on the master
uninterruptible power supply (UPS) side is accessed, and it sets up as follows.
1. UPS remote shutdown: Enable
2. Select Work as master UPS
3. Event occurs on Master UPS: Notify All
4. Event occurs on Slave UPS: Notify All
3, 4 section: we have set the behavior when a failure occurs in the power of the
uninterruptible power supply (UPS) of one of them. If the number of the power
of two sets (UPS) of uninterruptible power supplies is one, since generating
simultaneously is assumed, it is seldom necessary to be taken into consideration.
If it is another system, please set up whether to shut down both or to shut down
one according to a setup.
3
The Web page of [UPS management]-[ UPS remote shutdown] on the slave
uninterruptible power supply (UPS) side is accessed, and the waiting time to an
uninterruptible power supply (UPS) stop is set up.
4
The Web page of [UPS management]-[UPS remote shutdown] on the slave
uninterruptible power supply (UPS) side is accessed, and it sets up as follows.
1. UPS remote shutdown: Enable
2. Select Work as slave UPS
3. The IP address of master UPS is set up.
77