The example of a time chart
Setting conditions of Master UPS
Operation
:client shutdown / UPS stop
AC fail delay time (Min)
:10(
Initial value
)
1st warning (Sec)
:30(
Initial value
)
Warning period (Sec)
:30(
Initial value
)
Waiting time to a UPS stop
(Sec) :180(
Initial value
)
AC failure occurring time
:22:20:00
The setting conditions of a Slave UPS
Waiting time to a UPS stop (Sec)
:300
The setting conditions of a client computer
AC fail delay time
:30 sec
22 : 20 : 00
22 : 30 : 00
22 : 33 : 00
Master UPS ON
Master UPS OFF
The input power
failure occurs in
the master UPS
AC fail delay time
is ends.
Shutdown command
sending
Master UPS stop
22 : 35 : 00
Slave UPS ON
Slave UPS OFF
Shutdown command
reception
Slave UPS stop
22 : 30 : 30
Client computer
ON
Client computer OFF
Shutdown command
reception
The end of
delay time
Start OS stop
Client
computer
Power
OFF
79