Power ratings
240 W
480 W
Item
Type
Standard
Maintenance
forecast monitor
Total run time
monitor
Standard
Maintenance
forecast monitor
Total run time
monitor
Efficiency (typical) (rated input voltage)
80% min.
83% min.
Input
Voltage
*
1
100 to 240 VAC (allowable range 85 to 264 VAC)
Frequency
*
1
50/60 Hz (47 to 63 Hz)
Current
With 100-VAC input
3.8 A max.
7.4 A max.
With 200-VAC input
2.0 A max.
3.9 A max.
Power factor
0.95 min. (0.9 min. for BE models)
0.95 min.
Harmonic current regulation
Conforms to EN61000-3-2
Leakage current
With 100-VAC input
0.5 mA max.
With 200-VAC input
1.0 mA max.
Inrush current
*
2
With 100-VAC input
25 A max. (17.5 A max. for BE models)
25 A max.
With 200-VAC input
50 A max. (35 A max. for BE models)
50 A max.
Output
Voltage adjustment range
*
3
Models with indication monitor (except for BE models): Å}10%
(with V. ADJ)
Standard models (except for BE models):
−
10% to 15% (with
V.ADJ)
−
10% to 15% (with V.ADJ)
Ripple
2.0% (p-p) max. (at rated input/output voltage)
Input variation influence
0.5% max. (at 85- to 264-VAC input, 100% load)
Load variation influence
(rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence
0.05%/
°
C max.
Startup time
*
2
1,000 ms max. (at rated input/output voltage)
Hold time
*
2
20 ms min. (at rated input/output voltage)
Additional
functions
Overload protection
*
2
105% to 160% of rated load current, inverted L voltage drop, automatic reset
Overvoltage protection
*
2,
*
4
Yes
Output voltage indication
*
5
No
Yes (selectable)
*
6
No
Yes (selectable)
*
6
Output current indication
*
5
No
Yes (selectable)
*
7
No
Yes (selectable)
*
7
Peak-hold current indication
*
5
No
Yes (selectable)
*
8
No
Yes (selectable)
*
8
Maintenance forecast monitor indication
*
5 No
Yes (selectable)
No
Yes (selectable)
No
Maintenance forecast monitor output
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*
9
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
No
Total run time monitor indication
*
5
No
Yes (selectable)
No
Yes (selectable)
Total run time monitor output
*
5
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*
9
No
Yes (transistor
output), 30 VDC
max., 50 mA max.
*
9
Undervoltage alarm indication
*
5
No
Yes (selectable)
No
Yes (selectable)
Undervoltage alarm output terminals
No
Yes (transistor output), 30 VDC max., 50 mA
max.
*
9
No
Yes (transistor output), 30 VDC max., 50 mA
max.
*
9
Parallel operation
No
Series operation
Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature
Refer to the derating curve in Engineering Data (60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models). (with no icing or
condensation)
Storage temperature
−
25 to 65
°
C
Operating ambient humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard 240-W and 480-W
models: 30 mA, detection current for 240-W models with indication monitor: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance
100 M
Ω
min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions: 240 W
10 to 150 Hz, 0.35-mm single amplitude (3 G max.) for 80 min each in X, Y, and Z directions: 480 W
Shock resistance
150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
Yes (color: green)
EMI
Conducted
Emissions
Models with indication monitor: Conforms to EN61204-3
EN55011 Class A and based on FCC Class A, Conforms to
EN61204-3 EN55011 Class B
*
11
Standard models: Conforms to EN61204-3 EN55011 Group 1
Class B and based on FCC Class A
Conforms to EN61204-3 EN55011 Class A and based on FCC
Class A
Conforms to EN61204-3 EN55011 Class B
*
11
Radiated Emissions
Models with indication monitor: Conforms to EN61204-3
EN55011 Class A, Conforms to EN61204-3 EN55011 Class B
*
11
Standard models: Conforms to EN61204-3 EN55011 Group 1
Class B
Conforms to EN61204-3 EN55011 Class A
Conforms to EN61204-3 EN55011 Class B
*
11
EMS
Conforms to EN61204-3 high severity levels
Approved standards
*
11
UL: UL508 (Listing), UL60950-1
cUL: CSA C22.2 No.107.1,
cUR: CSA No. 60950-1,
EN/VDE: EN50178 (=VDE0160),
EN60950-1 (=VDE0805 Teil 1)
*
12
KOSHA S Mark
*
10
SEMI
*
11
F47-0706 (200-VAC input)
Weight
1,150 g max.
1,700 g max.