Table 1.6 Screw Sizes and Tightening Torques
Model
Screw Size
Tightening Torque
N
∙
m
2004 - 2082, 4002 - 4060
M4 × 20
1.0 - 1.3
2110 - 2211, 4075 - 4168
M4 × 25
1.0 - 1.3
2257 - 2415, 4208 - 4675
M5 × 25
2.0 - 2.5
◆
Safe Disable Input
Figure 1.7 TUV Mark
The TUV mark identifies that the product complies with the safety standards.
This section gives precautions to support the Safe Disable input. Contact the manufacturer for more information.
Table 1.7 Applied Safety Standards and Unified Standards
Safety Standards
Unified Standards
Functional Safety
IEC/EN 61508:2010 (SIL3)
IEC/EN 62061/A2:2015 (SILCL3)
IEC/EN 61800-5-2:2007 (SIL3)
Machine Safety
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
EMC
IEC/EN 61000-6-7:2015, IEC/EN61326-3-1:2008
SIL = Safety Integrity Level.
■
Safe Disable Specifications
The Safe Disable input provides the stop function compliant to
“
Safe Torque Off
”
defined in IEC/EN 61800-5-
2:2007. The Safe Disable input is designed to meet the requirements of EN ISO 13849-1 and IEC/EN 61508. It is
also equipped with the safety status monitor to detect safety circuit errors.
When you install the drive as a component in a system, you must make sure that the system complies with the
applicable safety standards.
Table 1.8 Specifications for the Safety Function
Item
Description
Input/output
•
Input: 2
Safe Disable input (H1, H2)
Signal ON level: 18 Vdc to 28 Vdc
Signal OFF level: -4 Vdc to +4 Vdc
•
Output: 1
MFDO safety monitor output for external device monitor (EDM)
Response time from opening the input to stopping the drive output
3 ms or less
Response time from opening H1 and H2 terminal inputs to operating the EDM
signal
20 ms or less
Failure probability
Less frequent operation request mode
PFD = 4.65E
-6
Frequent operation request mode or
continuous mode
PFH = 1.11E
-9
Performance level
The Safe Disable input complies with the performance level requirements of EN ISO 13849-
1.
HFT (hardware fault tolerance)
N = 1
Type of subsystem
Type B
EDM = External Device Monitoring
PFD = Probability of Failure on Demand
PFH = Probability of Dangerous Failure per Hour
EN
Содержание Q2A-A Series
Страница 2: ...This Page Intentionally Blank 2 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Страница 139: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 139 EU Declaration of Conformity EN...
Страница 140: ...6 Attachments 140 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Страница 141: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 141 EN...
Страница 142: ...6 Attachments 142 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Страница 143: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 143 EN...
Страница 144: ...6 Attachments 144 TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions...
Страница 145: ...6 Attachments TOMPYEUOQ2A03C AC Drive Q2A Installation and Operation Instructions 145 EN...