2-3-2. Connecting a device to the power supply output (BU200RW/BU300RW)
(1) Connect devices (computer, server, peripherals, etc.) that require backup to the power supply out-
put receptacle on the back of the unit.
Make sure that the total capacity of the devices connected to the output receptacle
does not exceed the output rated capacity of the BU200RW/BU300RW. If the over-
load indication (
) is displayed, reduce the number of connected devices.
Group A
Group B
Group C
Group control of power supply output See Page 15
See also
• Procedure for connection
to power supply output receptacle
Connect it directly.
Plug of connected device
“Power supply output” group Output receptacle
Group A
NEMA5-20R: 2 (Rated capacity: 20A)
Group B
NEMA5-20R: 2 (Rated capacity: 20A)
Group C
NEMA5-20R: 2 (Rated capacity: 20A)
“Power supply output” group Output receptacle
Group A
NEMA5-20R: 2 (Rated capacity: 20A)
Group B
NEMA5-20R: 2 (Rated capacity: 20A)
Group C
NEMA5-20R: 2 (Rated capacity: 20A)
BU200RW (Rated output capacity: 2kVA/1600W)
BU300RW (Rated output capacity: 3kVA/2400W)
BU200RW /BU300RW
(2) When using the included UPS monitoring software and the Windows standard UPS
service, use a connection cable to connect the unit to the PC.
See also "7. Using the UPS monitoring software and Contact Signal" on page 58.
* If you do not use the UPS monitoring software and Contact Signal, this step is not required.