2-2-1. Rackmount installation (EIA /JIS 19-inch rack/server rack)
●
BU75RW/BU100RW/BU200RW/BU300RW rack mounting procedure
(1) Insert the 4 included rail length
fi
xing screws and half-tighten them to hold the front and
rear rack rails in place.
①
Caution
●
Items included in the 19-inch rack support angle mounting bracket set
4 rail length fixing screws (small)
Rack rail (front) L ....................................... 1
Rack rail (front) R ...................................... 1
Rack rail (rear) ........................................... 2
Ear brackets .............................................. 2
Rail length fixing screws (small) ................ 4
Ear bracket flush mounting screws (M4).... 8
Rack fixing screws (M5) ............................ 8
Rack fixing nuts (M5) ................................ 8
Unit fixing screws (M6) .............................. 2
Unit fixing nuts (M6) .................................. 2
When performing rack installation, ensure that the UPS is supported and
stabilized by using both the support angles and the table clamps that
were included.
When connecting a battery unit and/or adding another battery unit, be
sure to place the battery unit in a position lower than the main unit.
●
When installing on a rack, make sure that the UPS is supported by the each unit individually.
●
When installing on a rack, make sure to use the support angles and table clamps included with
the product. Without the support angles, the front clamp alone cannot support the weight of the
UPS.
●
The mass of the UPS: BU75RW/BU100RW: Approx. 20kg
BUM100R: Approx. 26kg
BU200RW/BU300RW: Approx. 33kg BUM300R: Approx. 42kg
In a case where the UPS is to be mounted on a rack, place it on the
lowest part of the rack.
●
Dropping it may result in injury.
Be sure to use the supplied mounting screws.
●
Screws other than those supplied may not be strong enough to support the UPS, causing it to fall.