![Omron NQ HMI Скачать руководство пользователя страница 94](http://html1.mh-extra.com/html/omron/nq-hmi/nq-hmi_getting-started-manual_744230094.webp)
80
Note
• H5-07 = 0 (RS-485 connection): Create the applicable cable. Refer to (V1000 RS-485 connection) A-2-5.
• NQ-Series establishes a connection to the inverter by exchanging a default address
HR400001
. If this
address is not available in the used inverter, the connection will not be established. To establish the
connection proceed as follows.
1 Click in the
Nodes
folder and right-click the Node1 inverter.
2 Click
Edit
.
3 Click
PLC Specific Setting
.
4
5 Change
Default communication register
address to an available address in the inverter.
6 Click OK.
7 Download the application to the NQ-Series.
• The following messages are displayed on the NQ-Series’ screen if problems occur:
• !!! no connection
• ??? connection established, address unknown
Содержание NQ HMI