SECTION 11
Connection to the Machine Control Circuit
!WARNING
This product is designed for use on a 24 VDC, negative ground (protective
earth) electrical system only. Never connect the MS2800 system to a positive
ground (protective earth) system. With a positive ground (protective earth)
wiring scheme, certain simultaneous shorts of both safety outputs may not be
detected and the guarded machine may not stop, resulting in severe operator
injury.
!WARNING
Never use only a single safety output to control the machine. Should this sin-
gle output fail, the machine may not stop, resulting in severe operator injury.
The machine must be connected using both safety outputs.
The table below references Pin Numbers, Wire colors and signal names being
used with the MS2800 system.
The primary cables for the MS2800 system are industry standard non-
shielded cables with an M12 female connector. The receiver and transmitter
incorporate a 0,3 m pigtail with an M12 male connector.
We recommend to use the F39-JMR and F39-JMT cables to connect the
MS2800 system to the machine control system.
11-1 Interconnect cables for cascaded MS2800FS system
The segment-to-segment cable has a 4 contact M12 connector on each end.
The maximum cable length is 10 meters between segments.
The extension cables are available in lengths of 0.3 m, 0.5 m, 1 m, 2 m, 5 m
and 10 m. A MS2800FS system does not require an extension cable; it has a
150 mm integrated cable (pigtail).
MS2800FS systems are designed with internal circuit protection to protect
from damage when they are connected and disconnected (hot-swap) during
normal operation.
Receiver cable
Pin No. 1
Input power
Brown
+24VDC
Pin No. 2
Input power
Blue
GND
Pin No. 3
Input power
Green
Functional Earth
Pin No. 4
Output signal
White
OSSD2
Pin No. 5
Input signal
Yellow
Start
Pin No. 6
Input signal
Red
EDM
Pin No. 7
Output signal
Pink
Aux
Pin No. 8
Output signal
Black
OSSD1
Transmitter cable
Pin No. 1
Input power
Blue
GND
Pin No. 2
Input power
Brown
+24VDC
Pin No. 3
Input test
White
MTS
Pin No. 4
Input test
Black
MTS Return
Pin No. 5
Input power
Green
Functional Earth
Содержание MS2800E
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 19: ...2 Section ...
Страница 25: ...8 MS2800FS Cascaded Series Section 4 3 ...
Страница 33: ...16 Optical Synchronization Section 5 4 ...
Страница 39: ...22 Selecting Scan Codes Section 7 7 ...
Страница 41: ...24 Auxiliary Output Section 8 2 ...
Страница 51: ...34 General Mounting Considerations Section 10 3 ...
Страница 57: ...40 Using the test object Section 13 3 ...
Страница 59: ...42 Section ...
Страница 85: ...68 Accessories Section 15 9 ...
Страница 87: ...70 Section ...
Страница 91: ...74 Receiver Error Codes Section 17 5 ...
Страница 95: ...78 ...