K8DT-AS

12

Screw Mounting

1.

Pull out the two hooks on the back of the Relay to the outside until 
you hear them click in place.

2.

Insert M3 screws into the hook holes and secure the Relay.

Adjusting the Setting Knobs

• Use a flat-blade screwdriver to adjust the setting knobs. The knobs 

have a stopper that prevents them from turning beyond the full right 
or left position. Do not force a knob beyond these points.

• To reduce the error in the setting knob, always turn the setting knob 

from the minimum setting toward the maximum setting.

Connecting Wires to the Push-In Plus Terminal Block

Part Names of the Terminal Block

Connecting Wires with Ferrules and Solid Wires

Insert the solid wire or ferrule straight into the terminal block until the 
end strikes the terminal block.

If a wire is difficult to connect because it is too thin, use a flat-blade 
screwdriver in the same way as when connecting stranded wire.

Connecting Stranded Wires

Use the following procedure to connect the wires to the terminal block.

1.

Hold a flat-blade screwdriver at an angle and insert it into the 
release hole. The angle should be between 10° and 15°.
If the flat-blade screwdriver is inserted correctly, you will feel the 
spring in the release hole respond.

2.

With the flat-blade screwdriver still inserted into the release hole, 
insert the wire into the terminal hole until it strikes the terminal block.

3.

Remove the flat-blade screwdriver from the release hole.

Checking Connections

• After the insertion, pull gently on the wire to make sure that it will 

not come off and the wire is securely fastened to the terminal block.

• To prevent short circuits, insert the stripped part of a stranded or 

solid wire or the conductor part of a ferrule until it is hidden inside 
the terminal insertion hole. (See the following diagram.)

Removing Wires from the Push-In Plus Terminal Block

Use the following procedure to remove wires from the terminal block.
The same method is used to remove stranded wires, solid wires, and 
ferrules.

1.

Hold a flat-blade screwdriver at an angle and insert it into the 
release hole.

2.

With the flat-blade screwdriver still inserted into the release hole, 
remove the wire from the terminal insertion hole.

3.

Remove the flat-blade screwdriver from the release hole.

(1)

(1)

(2)

(2)

Two M3 screw holes or
two 3-dia. holes

108

Mounting Hole Dimensions

Note: 1.

Pull out the hooks to mount
the Relay with screws.

2.

Recommended tightening 
torque: 0.5 to 0.6 N·m.

Setting knob

Release hole

Terminal 
(Insertion) hole

Release hole

Terminal 
(Insertion) hole

<Upper side>

<Lower side>

Ferrule

Release hole

Terminal 
(Insertion) hole

Ferrule

Release hole

Terminal 
(Insertion) hole

<Upper side>

<Lower side>

Wire

Flat-blade screwdriver

(1)

(3)

(2)

Wire

Flat-blade screwdriver

(1)

(2)

(3)

10 to 15°

10 to 15°

Flat-blade 
screwdriver

Flat-blade 
screwdriver

<Upper side>

<Lower side>

Ferrule

Ferrule

<Upper side>

<Lower side>

Wire

<Upper side>

Wire

<Lower side>

Wire

Flat-blade screwdriver

(1)

(3)

(2)

Wire

Flat-blade screwdriver

(1)

(2)

(3)

10 to 15°

10 to 15°

Flat-blade 
screwdriver

Flat-blade 
screwdriver

<Upper side>

<Lower side>

Содержание K8DT-AS Seriesl

Страница 1: ...K8DT AS2 Options Order Separately Front Cover Refer to Safety Precautions on page 10 Refer to page 9 for commonly asked questions For the most recent information on models that have been certified for...

Страница 2: ...DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 100 mA AC DC I2 COM 10 to 100 mA AC DC Approx 1 Direct input 500 mA AC DC I3 COM 50 to 500 mA AC DC Approx 0 2 Direct input...

Страница 3: ...rules Applicable wire size 0 25 to 1 5 mm2 AWG24 to AWG16 Wire insertion force 8 N max for AWG20 wire Screwdriver insertion force 15 N max Wire stripping length 8 mm Ferrule length 8 mm Current capaci...

Страница 4: ...copper wires with a rating of 75 C or an equivalent rating Inside Inside 1 Current Input AS1 2 Output C Relay Output T Transistor Output 3 Power Supply Voltage A 100 to 240 VAC D 24 VAC DC No polarit...

Страница 5: ...ge Contacts 11 12 Set value Alarm indicator Lit Contacts 11 14 or transistor output Input Delay time 250 ms reference value Terminal block See note Terminal block See note Current knob SV Hysteresis k...

Страница 6: ...front of the Unit For the K8DT AS SW1 is not used Note Open the DIP switch cover to set the DIP switch Keep the DIP switch cover closed while the power supply to the Relay is ON Model Setting range I...

Страница 7: ...et Value SV of 50 and Overcurrent Operation Operation will be at 100 A and resetting at 90 A when the hysteresis HYS is set to 10 Operating Time The operating time is set using the operating time knob...

Страница 8: ...3 1 7 1 7 9 3 76 Two M5 screw holes or two 5 5 dia holes OMRON CT K8AC CT200L Mounting Hole Dimensions Note The OMRON Current Transformer CT is designed to be used with the K8DT AS3 Use terminals k an...

Страница 9: ...ely 30 A The startup current will exceed the overload capacity rating 150 for 1 s of the K8DT AS1 and K8DT AS2 and result in failure of the Relay To monitor the motor load use the K8DT AS3 Overload ca...

Страница 10: ...ails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay reg...

Страница 11: ...pply power to the product 22 Do not install the product immediately next to heat sources 23 Perform periodic maintenance 24 Do not wire anything to the release holes 25 When you insert a flat blade sc...

Страница 12: ...rom the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short ci...

Страница 13: ...re is basic insulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the in...

Страница 14: ...MEMO 14...

Страница 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 16: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...

Отзывы: