Input parameter settings values into the settings fields, and click the [Next] button.
Set in reference to the following table. Settings values may be changed at a later point, however ensure these are set prior
to starting measurement and monitoring.
Model
Parameter name
Settings value
Comprehensive
current
diagnosis model
Current range
Input settings values in accordance with CT being used.
0: 5 A rated, CT connected (K6CM-CICB005)
1: 25 A rated, CT connected (K6CM-CICB025)
2: 100 A rated, CT connected (K6CM-CICB100)
3: 200 A rated, CT connected (K6CM-CICB200)
4: 400 A rated, CT connected (K6CM-CICB400)
5: 600A rated, CT connected (K6CM-CICB600)
Current alarm (warning)/(critical) Input the motor status warning/critical threshold levels.
Vibration &
temperature
model
Temperature units
Select temperature units to use for motor temperature and
temperature gap.
0: °C
1: °F
Acceleration alarm (warning)/
(critical)
Input the motor status warning/critical threshold levels.
Velocity alarm (warning)/
(critical)
Motor temperature alarm (warn
-
ing)/(critical)
Temperature gap alarm
(warning)/(critical)
Insulation
resistance
model
Applicable circuit
Input settings values depending on motor drive method.
0: Three-phase three-wire S-phase ground
1: Three-phase four-wire N-phase grounded load side delta
connection
* For details, refer to the User's Manual.
Using inverter
Input settings values depending on the presence of an inverter.
0: No inverter
1: With inverter
Inverter special measurement
Input settings values to match the inverter frequency.
0: When inverter frequency differs from the commercial
frequency.
1: When inverter frequency and commercial frequency are close.
* For details, refer to the User's Manual.
Insulation resistance alarm
(warning)/(critical)
Input the motor status warning/critical threshold levels.
The following [Downloading to device] wizard screen will be displayed.
Confirm settings details, and if correct, click the [Execute] button.