Temperature Meter
K3MA-L
K-49
Panel
in
dicat
ors
Operation
■
Main Functions
Input Types and Ranges
Note:
The initial value is “
5:
thermocouple K (
−
200 to 1300
°
C/
−
300 to 2300
°
F).”
Temperature Unit Selection
Either centigrade (
°
C) or fahrenheit (
°
F) can be selected as the tem-
perature unit.
OUT Types (Comparative Output
Models Only)
OUT 1 can be set to operate in one of the three following modes in
accordance with the compared values:
•
Upper limit (High Acting):
The output is turned ON when the measurement value is greater
than its set value.
•
Lower limit (Low Acting):
The output is turned ON when the measurement value is less than
its set value.
•
Upper and lower limits (Outside Band Acting):
An upper limit (H set value) and lower limit (L set value) can be set
independently.
The output is turned ON when the measurement value is greater
than the upper-limit set value or less than the lower-limit set value.
Parameter
Setting
Input type
Meaning
in-t
0
Platinum-resistance
thermometer
Pt100
−
200 to 850
°
C
−
300 to 1500
°
F
1
−
199.9 to 500.0
°
C
−
1999 to 900.0
°
F
2
0.0 to 100.0
°
C
0.0 to 210.0
°
F
3
JPt100
−
199.9 to 500.0
°
C
−
199.9 to 900.0
°
F
4
0.0 to 100.0
°
C
0.0 to 210.0
°
F
5
Thermocouple
K
−
200 to 1300
°
C
−
300 to 2300
°
F
6
−
20.0 to 500.0
°
C
0.0 to 900.0
°
F
7
J
−
100 to 850
°
C
−
100 to 1500
°
F
8
−
20.0 to 400.0
°
C
0.0 to 750.0
°
F
9
T
−
200 to 400
°
C
−
300 to 700
°
F
10
−
199.9 to 400.0
°
C
−
199.9 to 700.0
°
F
11
E
0 to 600
°
C
0 to 1100
°
F
12
L
−
100 to 850
°
C
−
100 to 1500
°
F
13
U
−
200 to 400
°
C
−
300 to 700
°
F
14
−
199.9 to 400.0
°
C
−
199.9 to 700.0
°
F
15
N
−
200 to 1300
°
C
−
300 to 2300
°
F
16
R
0 to 1700
°
C
0 to 3000
°
F
17
S
0 to 1700
°
C
0 to 3000
°
F
18
B
100 to 1800
°
C
300 to 3200
°
F
Parameter
Setting
Meaning
d-u
c
Display in
°
C.
f
Display in
°
F.
Parameter
Setting
Meaning
out 1.t
hi
Upper limit: Alarm op-
erates at upper limit.
lo
Lower limit: Alarm op-
erates at lower limit.
hi-lo
Upper and lower lim-
its: Alarm operates at
upper and lower lim-
its.
Upper Limit (High Acting)
Lower Limit (Low Acting)
OUT1 value
Measurement
value
ON
OFF
Output
OUT1 value
Hysteresis
Hysteresis
Hysteresis
Hysteresis
Upper and Lower Limits
(Outside Band Acting)
OUT1 upper-limit
value
OUT1 lower-limit
value
ON
OFF
Output
ON
OFF
Output
Measurement
value
Measurement
value