Temperature Meter 

K3MA-L

Specifications

Ratings 

K3MA-L 100-240VAC, K3MA-L-C 100-240VAC

K3MA-L 24VAC/VDC, K3MA-L-C 24VAC/VDC

Supply voltage

100 to 240 VAC

24 VAC (50/60 Hz), 24 VDC

Operating voltage range

85% to 110% of the rated supply voltage

Power consumption 
(under maximum load)

6 VA max.

4.5 VA max. (24 VAC)
4.5 W max. (24 VDC)

Insulation resistance

20 M

 min. (at 500 VDC) between external terminal and case.

Insulation provided between inputs, outputs, and power supply.

Dielectric strength

2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.

Noise immunity

±

1,500 V on power supply terminals in normal or com-

mon mode.

±

µ

s, or 100 ns for square-wave noise with 1 ns.

±

480 V on power supply terminals in normal mode. 

±

1,500 V in common mode.

±

µ

s, or 100 ns for square-wave noise with 1 ns.

Vibration resistance

Vibration: 10 to 55 Hz, Acceleration: 50 m/s

2

 

5 min each in X, Y, and Z directions for 10 sweeps.

Shock resistance

150 m/s

2

 (100 m/s

2

 for relay contact outputs) 3 times each on 3 axes, 6 directions.

Ambient temperature

Operating:

10

°

C to 55

°

C (with no condensation or icing)

Storage:

25

°

C to 65

°

C (with no condensation or icing)

Ambient humidity

Operating:25% to 85% (with no condensation)

Approved safety standards

UL3121-1, conforms to EN61010-1 (Pollution degree 2/overvoltage category II) 
Conforms to VDE0106/P100 (finger protection)

EMC

(EMI)A1Industry
Emission Enclosure:CISPR 11 Group 1 class A: CISRP16-1/-2
Emission AC Mains:CISPR 11 Group 1 class A: CISRP16-1/-2
(EMS)A1Industry
Immunity ESD:EN61000-4-2:4 kV contact discharge
8 kV air discharge
Immunity RF-interference:EN61000-4-3:10 V/m (amplitude-modulated, 80 MHz to 1 GHz)
Electrical Fast Transient Noise:EN61000-4-4:2 kV (power line)
Immunity Burst Noise:1 kV line to line (I/O signal line)
Immunity Surge:EN61000-4-5:1 kV (power line)
2 kV line to ground (power line)
Immunity Conducted Disturbance:EN61000-4-6:3 V (0.15 to 80 MHz)
Immunity Voltage Dip/Interrupting:EN61000-4-11:0.5 cycle, 0, 180

°,

 100% (rated voltage)

Weight

Approx. 200 g

Содержание K3MA-L

Страница 1: ...EMA4X IP66 equivalent front panel Recognized to conform to U S and Canadian requirements un der the Component Recognition Program of UL CE marking Model Number Structure Model Number Legend 1 Input Type L Platinum resistance thermometer or thermocouple 2 Output Type None No output C With relay contact output SPDT 3 Supply Voltage 100 240VAC 100 to 240 VAC 24VAC VDC 24 VAC VDC Ordering Information ...

Страница 2: ...X Y and Z directions for 10 sweeps Shock resistance 150 m s2 100 m s2 for relay contact outputs 3 times each on 3 axes 6 directions Ambient temperature Operating 10 C to 55 C with no condensation or icing Storage 25 C to 65 C with no condensation or icing Ambient humidity Operating 25 to 85 with no condensation Approved safety standards UL3121 1 conforms to EN61010 1 Pollution degree 2 overvoltage...

Страница 3: ...rity display is displayed automatically with a negative input signal Zero display Leading zeros are not displayed Input shift Input shift equivalent to the setting value supported for all points within the sensor measurement range Hold function Max hold maximum value Min hold minimum value Hysteresis setting Programmable with front panel key inputs 0001 to 9999 Other functions Display color change...

Страница 4: ...re of 20 C 100 000 times min at a rated load switching frequency of 10 time min Power supply Output terminals Input terminals 100 to 240 VAC type or 24 VAC VDC type No polarity for 24 VDC connection Models with comparative output For thermocouple input For platinum resistance thermometer input OUT1 A B B A1 A2 E1 E2 E3 E4 E5 E6 E4 E5 E6 Recommended DC power supply eg OMRON S8VS Terminal No Name De...

Страница 5: ...300 to 1500 F 1 199 9 to 500 0 C 1999 to 900 0 F 2 0 0 to 100 0 C 0 0 to 210 0 F 3 JPt100 199 9 to 500 0 C 199 9 to 900 0 F 4 0 0 to 100 0 C 0 0 to 210 0 F 5 Thermocouple K 200 to 1300 C 300 to 2300 F 6 20 0 to 500 0 C 0 0 to 900 0 F 7 J 100 to 850 C 100 to 1500 F 8 20 0 to 400 0 C 0 0 to 750 0 F 9 T 200 to 400 C 300 to 700 F 10 199 9 to 400 0 C 199 9 to 700 0 F 11 E 0 to 600 C 0 to 1100 F 12 L 10...

Страница 6: ...o either red or green For comparative output models the display color can be set to change from green to red or from red to green according to the status of the comparison criterion Display Auto return Time This function automatically returns the display to the operation level s current value if no keys are pressed for a preset time called the dis play auto return time Move to Protect Level Time T...

Страница 7: ...X and MIN values when a measurement value is being displayed 5 Level Key Used to change the level 6 Mode Key Used to allow the main indicator to indicate parameters sequentially 7 Shift Key Used to enable a set value to be changed When changing a set value this key is used to move along the digits 8 Up Key Used to change a set value Used to set or clear a forced zero function when a measurement va...

Страница 8: ...oring the temperature of an industrial furnace Monitoring the bearing temperature for a generator motor E5EN K3MA L Alarm output Molding equipment K3MA L K3MA L Industrial furnace PID control Generator motor Alarm output Monitoring the temperature of an indus trial furnace sintering furnace Monitoring alarm function for disinfect ing equipment Monitoring failsafe checking abnormal temperatures in ...

Страница 9: ...cts the panel to secure the K3MA L Wiring Precautions Use crimp terminals Tighten the terminal screws to a torque of approximately 0 5 N m To avoid the influence of noise route signal lines and power lines separately Wiring Use the following M3 crimp terminals Unit Labels Provided The unit labels are not attached to the K3MA L Select the desired labels from the provided sheet Note For scales and g...

Страница 10: ...roduct during use or storage Doing so may deform or deteriorate the product 7 Do not use paint thinner for cleaning Use commercially available alcohol Mounting Mount the product to a panel that is 1 to 8 mm thick Install the product in a horizontal position Use crimp terminals that match screw sizes Noise Prevention Install the product as far as possible from devices that generate strong high freq...

Страница 11: ...inue Operation Displaying current values and setting OUT 1 value Continue Adjustment Setting communications writing control Continue Initial setting Making initial settings of input type output operating action and other parameters Stopped Advanced function setting Setting average processing display color settings and other ad vanced function parameters Stopped 123 4 Power ON Operation level Prote...

Страница 12: ...eters are not displayed for certain models 2 The K3MA L will stop measurement if the level is changed to the initial setting level or the advanced function setting level 3 If the input range is changed some parameters are set to default values Therefore set the input range first 4 Settings displayed in reversed colors are defaults Power ON Operation level Adjustment level Press Level Key for less ...

Страница 13: ...alization Average processing OUT1 type Temperature unit Temperature unit OUT1 type Upper Limit Lower Limit Upper Lower Limits Models with the compara tive out put function MODE MODE MODE MODE Models with the compar ative out put function Display color change Display auto return time Move to protect level time Green red Green Red green Red Unit s Unit s OUT1 Hysteresis Unit times MODE MODE MODE MOD...

Страница 14: ... than preset time Paramet er Setting Operation level Moving to adjustment level Process value display Set value display oapt 0 Allowed Allowed Allowed 1 Allowed Allowed Prohibited 2 Allowed Prohibited Prohibited Parameter Setting Shift to initial setting level Shift to advanced function setting level icpt 0 Allowed Allowed 1 Allowed Prohibited 2 Prohibited Prohibited Parameter Setting Setting chan...

Страница 15: ...ain indicator Error contents Countermeasures Not lit e111 RAM memory error Repair is necessary Consult your OMRON sales repre sentative 5 e111 EEPROM memory error When this error is displayed press the Level Key for 3 seconds and the settings will be restored to the factory settings If the error cannot be recovered re pair is necessary Consult your OMRON sales repre sentative Not lit Flashes s err...

Страница 16: ...pplication or use of the products At the customer s request OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product machine system or other application or use The following ar...

Отзывы: