- 41 -
Weekly
2 chnls
Yearly
2 chnls
Yearly
4 chnls
Example 1 Regular setting: ON at 9:00; OFF at 17:00
The Time Switch turns OFF an output at 15:00
today because of completing the production
earlier than usual.
Change the setting of the OUT ON/OFF switch from AUTO to OFF at 15:00.
Turn the OUT ON/OFF switch from OFF to AUTO with
pressed. (Output keeps in OFF state.)
The regular operation will be performed from the next ON time.
This function forcibly turns ON/OFF an output without changing
the state of automatic operations.
9:00
15:00 17:00
Today
9:00
17:00
Tomorrow
The next ON/OFF operation
is automatically executed
according to the previous
settings.
ON
AUTO
OFF
Example 2 Regular setting: ON at 9:00; OFF at 17:00
The Time Switch turns ON an output at 7:00 am
today because of more production than usual.
Change the setting of the OUT ON/OFF switch from AUTO to ON at 7:00.
Turn the OUT ON/OFF switch from ON to AUTO with
pressed. (Output keeps in ON state.)
The regular operation will be performed from the next OFF time.
9:00
0
0
:
7
1
0
0
:
7
Today
9:00
17:00
Tomorrow
The next ON/OFF operation
is automatically executed
according to the previous
settings.
ON
AUTO
OFF
5-8. Override and Automatic Return Operation
WRITE