2-2-1 Indications
Indications of both CompoNet and CC-Link status are provided on the Gateway Unit.
CompoNet Communications Section
z
CompoNet Communications Indicators
The following LED indicators are provided for CompoNet communications.
MS (Module Status): Shows the status of the node itself (two colors: green and red).
NS (Network Status): Shows the status of communications (two colors: green and red).
SD (Send Data):
Shows the transmission status from the Gateway Unit to CompoNet (one
color: yellow).
RD (Receive Data):
Shows the reception status from CompoNet to the Gateway Unit (one color:
yellow).
REG (Registration):
Shows if the registration table is enabled or disabled (one color: green).
Indicator
Status
Status definition
Meaning
MS
Lit green
Normal
The Unit is operating normally.
Lit red
Fatal error
Unit hardware error, such as a watchdog timer error
(WDT)
Not lit
Power OFF/Preparing
Power OFF, resetting, or initializing
NS
Lit green
Online with remote I/O
communications in
progress
Power is being supplied, remote I/O communications have
started, there are no communications errors at any Slave
Unit or Repeater Unit, there are no registration table
errors, and there are no node address duplication errors
for Slave Units or Repeater Units.
Flashing
green
Online with no remote I/O
communications in
progress
Remote I/O communications have not started or have
stopped.
Flashing
red
Non-fatal communications
error
A communications error has occurred at one or more
Slave Units or Repeater Units.
A verification error (non-existent or unregistered Slave
Unit) has occurred at one or more Slave Units.
Communications have stopped due to a communications
error, an illegal configuration error (number of Repeater
Units) has occurred, or an address duplication error has
occurred at one or more Slave Units or Repeater Units.
Not lit
Power OFF/Preparing
Power OFF, resetting, or initializing
SD
Lit yellow
Normal transmission
Frames are being sent normally from the Gateway Unit to
CompoNet.
Not lit
No transmission
Data is not being sent by the Gateway Unit
RD
Lit yellow
Normal reception
Frames are being received normally from CompoNet
Slave Units.
Not lit
No reception
Data is not being received by the Gateway Unit.
REG
Lit green
Registration table enabled The registration table has been created and is enabled.
The registration table has been created.
Flashing
green
Registration table creation The registration table is being created.
Not lit
Registration table
disabled
The registration table is disabled or has not been created.
Содержание GQ-CRM21
Страница 1: ...OPERATION MANUAL Cat No W489 E1 01 GQ CRM21 CompoNet Gateway Unit for CC Link ...
Страница 21: ...1 Overview 1 1 Overview 1 1 ...
Страница 25: ...2 Description of Gateway Unit 2 1 Specifications 2 1 2 2 Component Names and Functions 2 4 ...
Страница 38: ...2 13 CompoNet Gateway Unit for CC Link Operation Manual 2 2 Component Names and Functions 2 ...
Страница 102: ......