2 - 3
CompoNet Gateway Unit for CC-Link Operation Manual
2-
1 Specif
ica
ti
ons
2
2-1-3 CompoNet Communications Specifications
* Lengths given in parentheses are for when two Repeater Units are used.
Item
Specification
Communications protocol
CompoNet protocol
Baud rate
93.75 kbps, 1.5 Mbps, 3 Mbps, or 4 Mbps*1
*1
A baud rate of 4 Mbps is not supported for branch lines and thus cannot be used for
Slave Units with Cables.
Modulation
Baseband
Coding
Manchester code
Error control
Manchester code rules, CRC
Communications media
Round Cable I (2-conductor cable, JIS C3306)
Round Cable II (4-conductor cable, JIS C3306)
Flat Cable I (DCA4-4F10 Standard Flat Cable)
Flat Cable II (DCA5-4F10 Sheathed Flat Cable)
Communi-
cations
distance
Baud rate
Max.
segment
length
Branch
length per
segment
Total
branch
length per
segment
Branch
location
restriction
Connected
nodes per
branch
Max. sub-
trunk length
per segment
Total sub-
trunk length
per segment
4 Mbps*
30 m
(90 m)
0 m
0 m
---
---
---
---
3 Mbps*
30 m
(90 m)
0.5 m
8 m
3 branches/m 1
0 m
0 m
1.5 Mbps
(Round
Cable I)*
No
branches
100 m
(300 m)
---
---
---
---
---
---
Branches 30 m
(90 m)
2.5 m
25 m
3 branches/m 3
---
---
1.5 Mbps (Round
Cable II or Flat
Cable I/II)
30 m
(90 m)
2.5 m
25 m
3 branches/m 3
0.1 m
2 m
93.75 kbps (Round
Cable I)
500 m
(1,500 m)
6 m
120 m
3 branches/m 3
---
---
93.75 kbps (Round
Cable II or Flat
Cable I/II)
Unrestricted wiring is enabled for a total length of 200 m per segment.
Maximum I/O capacity
Word Slave Units: 1,024 inputs and 1,024 outputs (2,048 I/O points total)
Bit Slave Units: 256 inputs and 256 outputs (512 I/O points total)
When the Gateway Unit is used, I/O capacities are as follows depending on the CompoNet
communications mode.
Max. number of connected
nodes
Word Slave Units: 64 input nodes and 64 output nodes
Bit Slave Units: 128 input nodes and 128 output nodes
When the Gateway Unit is used, the maximum number of connected nodes is as follows
depending on the CompoNet communications mode.
Max. number of connected
nodes per trunk line or sub-trunk
line
32 nodes (number of Slave Unit and Repeater Unit nodes)
Communications
mode 0 or 4
Communications
mode 1 or 5
Communications
mode 2 or 6
Communications
mode 3
Word Slave
Units
1,024 inputs and
1,024 outputs
512 inputs and
512 outputs
256 inputs and
256 outputs
128 inputs and
128 outputs
Bit Slave Units
256 inputs and
256 outputs
192 inputs and
192 outputs
96 inputs and 96
outputs
32 inputs and
32 outputs
Communications
mode 0 or 4
Communications
mode 1 or 5
Communications
mode 2 or 6
Communications
mode 3
Word
Slave
Units
IN0 to IN63 and
OUT0 to OUT63
IN0 to IN31 and
OUT0 to OUT31
IN0 to IN15 and
OUT0 to OUT15
IN0 to IN7 and
OUT0 to OUT7
Bit Slave
Units
IN0 to IN127 and
OUT0 to OUT127
IN0 to IN95 and
OUT0 to OUT95
IN0 to IN47 and
OUT0 to OUT47
IN0 to IN15 and
OUT0 to OUT15
Содержание GQ-CRM21
Страница 1: ...OPERATION MANUAL Cat No W489 E1 01 GQ CRM21 CompoNet Gateway Unit for CC Link ...
Страница 21: ...1 Overview 1 1 Overview 1 1 ...
Страница 25: ...2 Description of Gateway Unit 2 1 Specifications 2 1 2 2 Component Names and Functions 2 4 ...
Страница 38: ...2 13 CompoNet Gateway Unit for CC Link Operation Manual 2 2 Component Names and Functions 2 ...
Страница 102: ......