16

Solid State Relays

 

G3PA

Safety Precautions

Close Mounting

SSR Mounting Pitch

Panel Mounting

 (At a rated ambient temperature of 40

°

C).

Relationship between SSRs and Ducts

Ventilation

Note: 1.

If the air inlet or air outlet has a filter, clean the filter regularly 
to prevent it from clogging and ensure an efficient flow of air.

2.

Do not locate any objects around the air inlet or air outlet, 
otherwise the objects may obstruct the proper ventilation of 
the control panel.

3.

A heat exchanger, if used, should be located in front of the 
SSR Units to ensure the efficiency of the heat exchanger.

Please reduce the ambient temperature of SSRs.
The rated load current of an SSR is measured at an ambient 
operating temperature of 40

°

C. 

An SSR uses a semiconductor in the output element. This causes 
the temperature inside the control panel to increase due to heating 
resulting from the passage of electrical current through the load. To 
restrict heating, attach a fan to the ventilation outlet or air inlet of 
the control panel to ventilate the panel. This will reduce the ambient 
temperature of the SSRs and thus increase reliability. (Generally, 
each 10

°

C reduction in temperature will double the expected life.)

Example: For 10 SSRs with load currents of 20 A, 

0.31 

×

 10 = 3.1

Thus, 4 fans would be required.

Size of fans: 92 mm

2

, Air volume: 0.7 m

3

/min, 

Ambient temperature of control panel: 30

°

C

If there are other instruments that generate heat in the control 
panel other than SSRs, additional ventilation will be required.

EMC Directive Compliance

The G3PA complies with EMC Directives under the following 
conditions.

A film capacitor is connected to both sides of the load power supply 
output.

The input power supply cable length for 200-V models is less than 
10 m.

Loss Time

Loss time will increase if the G3PA is used at a low voltage or 
current. Check that there will be no problems with operation before 
using the G3PA. 

SSR

60 mm min.

Vertical direction

30 mm min.

80 mm min.

min.

Duct or airflow obstruction

SSR

SSR

SSR

Mounting surf

ace

Mounting surf

ace

Mounting surf

ace

Duct or 
airflow 
obstruction

Duct or
airflow 
obstruction

Vertical 

direction

Airflow

(A height of no 
more than half
the SSR's height is
recommended.)

Duct Height

If the ducts cannot be 
shortened, place the SSR 
on a metal base so that it 
is not surrounded by the 
ducts.

Use short ducts. 

Do not surround the SSR 
with ducts, otherwise the 
heat radiation of the SSR 
will be adversely affected.

Countermeasure  (1)

Countermeasure (2)

 50 mm max.

SSR

SSR

SSR

Air inlet

Be aware of air flow

Duct or 
air flow 
obstruction

Ventilation 
outlet
(axial fan)

SSR rated current (A)

10 A

20 A

30 A

40 A

60 A

Required number of fans 
per SSR

0.16

0.31

0.47

0.62

0.93

Output

Input

G3PA

Load

Input cable length

Film capacitor

 1 

µ

F, 250 VAC

   (G3PA-2

@@

)

Loss time

Содержание G3ZA

Страница 1: ...ing an EJ1 Modular Temperature Controller Control method Phase Control Response is fast and high precision temperature control is possible Harmonics and noise are problems Optimum Cycle Control High precision Zero Cross Control Outputs are turned ON and OFF each half cycle Zero cross control is performed Noise is suppressed while achieving high speed response with high precision temperature contro...

Страница 2: ...ÜV UL and CSA 1 2 3 4 G3ZA 5 6 7 Name Number of control channels Heater burnout detection Load power supply voltage Model Multi channel Power Controller 4 Supported 100 to 240 VAC G3ZA 4H203 FLK UTU 400 to 480 VAC G3ZA 4H403 FLK UTU 8 Not supported 100 to 240 VAC G3ZA 8A203 FLK UTU 400 to 480 VAC G3ZA 8A403 FLK UTU Upgraded Functionality Refer to page 7 for details Upgrade functions are marked wit...

Страница 3: ...y 25 to 85 Storage temperature 25 to 65 C with no icing or condensation Elevation 2 000 m max Accessories Instruction Sheet V2 V2 V2 Current indication accuracy Current Range 0 to 50 A 3 A 0 to 150 A 9 A 0 to 100 6 See note for models with heater burnout detection Insulation resistance 100 MΩ min at 500 VDC between primary and secondary Dielectric strength 2 000 VAC 50 60 Hz for 1 min between prim...

Страница 4: ...bles switching to phase control when the current value is below the set value and switching to optimum cycle control when the current value is above the set value The default setting is 20 0 Example For channel 1 soft start optimum cycle control is performed under the following conditions control switching MV 40 0 MV 100 soft startup time 20 s 1 Ch 1 Control Switching MV Threshold is set to 40 0 a...

Страница 5: ...e 100 to 240 VAC 50 60 Hz Models with Load Power Supply Voltage of 100 to 240 V Power supply voltage 100 to 240 VAC 50 60 Hz Models with Load Power Supply Voltage of 400 to 480 V Load power supply voltage 400 to 480 VAC 50 60 Hz 19 20 21 22 23 24 CH5 CH6 COM CH7 CH8 COM CH1 CH2 COM CH3 CH4 COM 13 14 15 16 17 18 CH1 CH2 COM CH3 CH4 COM CH1 CH2 COM CH3 CH4 COM 19 20 21 22 23 24 13 14 15 16 17 18 CT ...

Страница 6: ...Load Trigger signal SSR three phase CT 4 channel model only Load power supply Eight SSRs Eight SSRs Eight SSRs SW2 SW1 ERROR OCC SD RD READY G3ZA PC PLC PT PC EJ1N TC4 or EJ1N TC2 EJ1C EDU Port A connector USB connection possible using a E58 CIFQ1 sold separately Port B RS 485 CompoWay F COM1 COM2 COM3 PWR RUN ERR ALM SW1 ON SW2 2 1 3 4 5 6 7 8 EJ1 TC4 0 1 2 3 4 5 6 7 8 9 A B C DEF COM1 COM2 COM3 ...

Страница 7: ... with V2 Identifying Upgraded Models Check the label on the Power Controller or the box to determine the version Models not marked Ver 2 0 are version 1 0 Box Label Power Controller Label Dimensions Note All units are in millimeters unless otherwise indicated Multi channel Power Controllers V2 V2 Version OMRON Corporation MADE IN JAPAN Version Mounting Hole Dimensions For Direct Mounting 4 6 dia 1...

Страница 8: ...o 5 5 dia holes 57 30 dia 14 5 14 5 6 8 5 50 33 5 34 5 81 5 13 5 86 54 63 11 4 7 Four M4 6 screws 17 20 26 max 9 3 1 7 1 7 9 3 76 Mounting Hole Dimensions Current Transformer CT G3ZA CT150L Note The G3ZA CT150L is for use only in combination with the G3ZA Wire terminal k and terminal l Do not use terminal kt and terminal lt 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Dimensio...

Страница 9: ... the product as possible 11 For a safety disconnection of the power line in the application the equipment must be provided with disconnecting devices suitable for isolation e g circuit breakers defined in IEC60947 2 power switches defined in IEC60947 3 power plugs etc Version 1 0 Usage Precautions Version 1 0 is for single phase loads only Connect a single phase zero cross SSR Do not connect a thr...

Страница 10: ...t an End Plate on each side of the G3ZA so that it does not slide on the DIN Track To mount an End Plate hook the bottom of the End Plate on the bottom of the DIN Track 1 place the top of the End Plate on the DIN Track 2 and then pull down on the End Plate Tighten the screw on the End Plate to secure it Note Always mount one End Plate on each side of the G3ZA Installation Example When installing t...

Страница 11: ...art function of the G3ZA Ordering Information List of Models Note 1 The rated output load depends on the ambient temperature Refer to Engineering Data 2 The loss time will increase if 75 VAC or less is used Check operation using the actual load Isolation Zero cross function Indicator Rated output load See note 1 Rated input voltage Model Phototriac coupler No Yes 10 A at 24 to 240 VAC See note 2 5...

Страница 12: ... at 40 C 220 A 60 Hz 1 cycle G3PA 240B L VD 0 5 to 40 A at 40 C 440 A 60 Hz 1 cycle G3PA 260B L VD 0 5 to 60 A at 40 C 440 A 60 Hz 1 cycle Item G3PA 210BL VD G3PA 220BL VD G3PA 240BL VD G3PA 260BL VD Operate time 1 ms max Release time 1 2 of load power source cycle 1 ms max Output ON voltage drop 1 6 V RMS max Leakage current 5 mA max at 100 VAC 10 mA max at 200 VAC 10 mA max at 100 VAC 20 mA max ...

Страница 13: ...ient temperature C Load current A 80 60 40 20 25 0 100 80 60 40 20 0 20 30 Ambient temperature C Load current A 150 100 50 0 5 000 1 000 500 200 100 50 30 10 Energized time ms Inrush current A Peak 200 150 100 50 0 5 000 1 000 500 200 100 50 30 10 Energized time ms Inrush current A Peak 400 300 200 100 0 5 000 1 000 500 200 100 50 30 10 Energized time ms Inrush current A Peak Linking terminal B1 T...

Страница 14: ...nting holes Note Without Terminal Cover Note With Terminal Cover G3PA 220BL VD Terminal Arrangement Internal Connections Linking terminal B1 Two M5 12 Linking terminal B2 Two M3 5 7 5 67 35 0 2 4 6 dia 4 6 5 6 elliptical hole 100 max 100 max 89 91 38 90 0 2 80 13 13 18 7 6 47 max 4 5 Two 4 5 dia or M4 90 0 3 35 0 3 Trigger circuit Input circuit Mounting holes G3PA 240BL VD Terminal Arrangement Int...

Страница 15: ... 6 elliptical hole 100 max 100 max 89 91 38 90 0 2 80 13 13 18 7 6 110 max 4 5 Two 4 5 dia or M4 90 0 3 35 0 3 A1 A2 1 2 Trigger circuit Input circuit G3PA 260BL VD Terminal Arrangement Internal Connections Mounting holes Note Without Terminal Cover Note With Terminal Cover ...

Страница 16: ...ired Size of fans 92 mm2 Air volume 0 7 m3 min Ambient temperature of control panel 30 C If there are other instruments that generate heat in the control panel other than SSRs additional ventilation will be required EMC Directive Compliance The G3PA complies with EMC Directives under the following conditions A film capacitor is connected to both sides of the load power supply output The input powe...

Страница 17: ...Solid State Relays G3PA 17 ...

Страница 18: ...18 Solid State Relays G3PA ...

Страница 19: ...Solid State Relays G3PA 19 ...

Страница 20: ...ABILITY In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROP...