7 Outputs
7-1 Safety Outputs
13
7 Outputs
7-1 Safety Outputs
The F3SL system receiver supplies two independent PNP-type, safety outputs to provide run/stop signals to the
guarded machine. In the machine run state, the safety outputs are electrically conducting and source 500 milli-
amps of current at 24 VDC. In the machine stop state, the outputs are not electrically conducting.
Note:
The safety outputs must have a minimum load or the F3SL system will enter a alarm condition. For the
purpose of testing prior to final installation, this load can be supplied by a 10K ohm resistor (included in
documentation kit). See Figure 7-1 for details
.
Figure 7-1 Connection of load to safety outputs for testing.
7-2 Auxiliary Output
This is not a safety output. F3SL systems suplies one PNP-type auxiliary output.In the on state, this Auxiliary
output will source up to 100mA, and will be on when the safety outputs are on. (Follow mode)
WARNING
This product is designed for use on a 24 VDC, negative ground (protective earth) electrical system only.
Never connect the F3SL to a positive ground (protective earth) system. With a positive ground (protective
earth) wiring scheme, certain simultaneous shorts of both safety outputs may not be detected and the
guarded machine may not stop resulting is severe operator injury.
24 VDC
SUPPLY
OSSD1
OSSD2
0 V
24 V+
10K ohm
10K ohm