Appendix E
Hardware Test
78
Control Output
Output value:
0% to 100%
Current output value:
4
+0
/
–0.6
to 20
+2
/
–0
mA
Output with Control Interrupted
Output value:
0%
Current output value:
4
+0
/
–0.6
mA
Output with Control Interrupted by Error
Output with Temperature Controller error
Output value:
–16%
Current output value:
1
±
0.5 mA