Appendix A
Specifications
61
E5ZE Characteristics
Item
Specification
Measurement
range
–20
°
C (lower limit of the setting range) to 20
°
C (upper limit of the setting range)
–40
°
F (lower limit of the setting range) to 40
°
F (upper limit of the setting range)
Setting
Setting unit
1
0.1
range
Celsius
Fahrenheit
Celsius
Fahrenheit
(See note 2.)
Ther-
K
–200 to 1,300
°
C
–300 to 2,300
°
F
–200.0 to 1,300.0
°
C
–300.0 to 2,300.0
°
F
mocou- J
–100 to 850
°
C
–100 to 1,500
°
F
–100.0 to 850.0
°
C
–100.0 to 1,500.0
°
F
ple
R
0 to 1,700
°
C
0 to 3,000
°
F
0.0 to 1,700.0
°
C
0.0 to 3,000.0
°
F
S
0 to 1,700
°
C
0 to 3,000
°
F
0.0 to 1,700.0
°
C
0.0 to 3,000.0
°
F
T
–200 to 400
°
C
–300 to 700
°
F
–200.0 to 400.0
°
C
–300.0 to 700.0
°
F
E
0 to 600
°
C
0 to 1,100
°
F
0.0 to 600.0
°
C
0.0 to 1,100.0
°
F
B
100 to 1,800
°
C
300 to 3,000
°
F
100.0 to 1,800.0
°
C
300.0 to 3,000.0
°
F
N
0 to 1,300
°
C
0 to 2,300
°
F
0.0 to 1,300.0
°
C
0.0 to 2,300.0
°
F
L
–100 to 850
°
C
–100 to 1,500
°
F
–100.0 to 850.0
°
C
–100.0 to 1,500.0
°
F
U
–200 to 400
°
C
–300 to 700
°
F
–200.0 to 400.0
°
C
–300.0 to 700.0
°
F
W/Re5-26
0 to 2,300
°
C
32 to 4,100
°
F
0.0 to 2,300.0
°
C
0.0 to 4,100.0
°
F
PL-II
0 to 1,300
°
C
0 to 2,300
°
F
0.0 to 1,300.0
°
C
0.0 to 2,300.0
°
F
Plati-
num
resis-
Pt 100
–100 to 500
°
C
–100 to 900
°
F
–100.0 to 500.0
°
C
–100.0 to 900.0
°
F
tance
ther-
mome-
ter
JPt 100
–100 to 500
°
C
–100 to 900
°
F
–100.0 to 500.0
°
C
–100.0 to 900.0
°
F
Measurement
accuracy
Thermocouple:
±
0.3% of the process value or
±
2
°
C, whichever is larger
±
1 digit max.
±
0.3% of the process value or
±
3.6
°
F, whichever is larger
±
1 digit max.
Platinum resistance thermometer:
±
0.3% of the process value or
±
0.8
°
C, whichever is larger
±
1 digit max.
±
0.3% of the process value or
±
1.5
°
F, whichever is larger
±
1 digit max.
Setting
accuracy
There is no difference between the setting accuracy and measurement accuracy.
Guaranteed
setting accuracy
range
Same as the setting range.
Influence of
conductor
resistance
Thermocouple:
±
0.1
°
C/
Ω
or
±
0.2
°
F/
Ω
max.
Platinum resistance thermometer:
±
1.0
°
C/
Ω
or
±
1.8
°
F/
Ω
max. per line
Input shift
–99.9 to 99.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Hysteresis
0.0 to 99.9
°
C/
°
F for ON/OFF control only (in units of 0.1
°
C/
°
F)
Cooling
coefficient
0.0 to 10.0 (in units of 0.1)
Proportional
band
(P constant)
0.0
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Cooling proportional band: Proportional band x Cooling factor
Integral time
(I constant)
0 to 3,999 s (in units of 1 s)
(cannot be set for heating and cooling independently)
Derivative time
(D constant)
0 to 3,999 s (in units of 1 s)
(cannot be set for heating and cooling independently)
Control period
1 to 99 s (in units of 1 s)
Cooling control period: 1 to 99 s (in units of 1 s)
Sampling period
200 ms for 8 control points