E5CSL/E5CWL

5

External Connections

A voltage output (control output 1) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect 
any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured 
temperature values as a result of leakage current.

Nomenclature

E5CSL
E5CWL

Dimensions

+

A

B

B

Pt input

Input power supply: 
100 to 240 VAC, 
50/60 Hz

DO NOT
USE

Control output

+

TC input

1

Control Output
• Relay output: 250 VAC, 3 A (resistive load)
• Voltage output (for driving SSR): 12 VDC, 21 mA

2

3

4

5

9

10

E5CSL

+

A

B

B

Pt input

Alarm Output

• 

Relay output: 250 VAC, 1 A 

(resistive load)

Input power supply: 
100 to 240 VAC, 
50/60 Hz

DO NOT
USE

Control output

+

TC input

1

Control Output
• Relay output: 250 VAC, 3 A (resistive load)
• Voltage output (for driving SSR): 12 VDC, 21 mA

2

3

4

5

7

8

9

10

E5CWL

(10) 

D

 

Down Key: Reduces the setting.

(11) 

U

 

Up Key: Increases the setting.

(12) 

O

+

M

 

Press these keys for at least 3 seconds in Operation Level or Adjustment Level to go to Protect Level. 

 

Press these keys for at least 1 second in Protect Level to return to Operation Level. 

(13) 

M

+

D

 

Press these keys for at least 2 seconds to start or stop autotuning.*1

(14) 

M

+

U

 

Press these keys for at least 2 seconds to start or stop operation.*2

(3)

(7)

(4)

(9)

(8)

(12)

(13)

(14)

(11)

(12)

(13)

(14)

(11)

(10)

(2)

(1)

(10)

(6)

(6)

(7)

(8)

(5)

(1)

(9)

E5CSL

E5CWL

*1: These keys are disabled when starting and stopping autotuning has been disabled with operation control 
     

 

key protection. 

*2: These keys are disabled when starting and stopping operation has been disabled with operation control 
     

 

key protection. 

(1) Display No. 1 

Displays the process value (PV) or parameter. For the E5CSL, 

 

the set point or parameter setting is also displayed.

(2) Display No. 2 

Displays the set point (SP) or parameter setting.

(3) Deviation  

Show the relation between the process value and the set point. 

Indicators 

    Lit: The process value is more than 5°C/°F higher than the set point.

 

    Lit: The process value is more than 5°C/°F lower than the set point.

 

    Lit: The process value is within 5°C/°F of the set point.

 

The relevant deviation indicator will flash during autotuning.

(4) SP 

Lit while the set point is displayed on display No. 1 (E5CSL only). 

(5) ALM 

Lit while the alarm is ON. Not lit while the alarm is OFF. 

(6) OUT 

Lit while the control output is ON. Not lit while the control output is 

OFF. 

(7) STOP 

Not lit during operation. Lit while operation is stopped. 

(8) 

O

 

Level Key: Changes the setting level.

(9) 

M

 

Mode Key: Changes the parameter within the setting level.

Package Contents

  • Temperature Controller
  • Adapter
  • Instruction Manual

4

60

64

58

44.8×44.8

48×48

Adapter

• Solderless terminal size: M3.5
• Terminal Cover: E53-COV19 (sold separately)
• Front Panel: E53-COV20 (sold separately)

*The dimensions are the same 

for the E5CSL.

60 min.

+1.0

0

45

+0.6

0

45

+0.6

0

45

+0.6

0

Panel Cutout

Individual Mounting

Group Mounting

Recommended panel thickness is 
1 to 5 mm.

Group mounting is not possible in 
the vertical direction. (Maintain the 
specified mounting space between 
Controllers.)

When two or more Controllers are 
mounted, make sure that the 
surrounding temperature does not 
exceed the ambient operating 
temperature given in the 
specifications.

Содержание E5CSL

Страница 1: ...At the end of this document you will find links to products related to this catalog You can go directly to our shop by clicking HERE HERE ...

Страница 2: ... VDC 21 mA 2 Sensor type TC Thermocouple K J T R or S P Platinum resistance thermometer Pt100 Models with Dual Display 1 Control Output R Relay output 250 VAC 3 A Q Voltage output for driving SSR 12 VDC 21 mA 2 Alarm E5CWL only 1 Relay output 250 VAC 1 A resistive load 3 Sensor type TC Thermocouple K J T R or S P Platinum resistance thermometer Pt100 48 48 mm E5CSL 48 48 mm E5CWL Sensor Inputs The...

Страница 3: ...E53 COV19 Model E53 COV20 Model Y92F 45 Power supply voltage 100 to 240 VAC 50 60 Hz Operating voltage range 85 to 110 of rated supply voltage Power con sumption E5CSL 3 5 VA E5CWL 3 5 VA Sensor input Models with thermocouple inputs Thermocouple K J T R or S Models with platinum resistance thermometer inputs Platinum resistance thermometer Pt100 Control output Relay output SPST NO 250 VAC 3 A resi...

Страница 4: ...0 0 to 400 0 0 0 to 750 0 4 T 200 to 400 300 to 700 5 199 9 to 400 0 199 9 to 700 0 6 R 0 to 1 700 0 to 3 000 7 S 0 to 1 700 0 to 3 000 Model temperature input Set value Input type Range C F Pt input 8 Pt100 200 to 850 300 to 1500 9 199 9 to 500 0 199 9 to 900 0 Setting Alarm type Positive alarm value X Negative alarm value X 0 No alarm Output OFF 1 Deviation upper lower limit Always ON 2 Deviatio...

Страница 5: ... input type Sampling period 250 ms Affect of signal source resistance Thermocouple 0 1 C Ω max 100 Ω max See note 2 Platinum resistance thermometer 0 6 C Ω max 10 Ω max Insulation resistance 20 MΩ min at 500 VDC Dielectric strength 2 300 VAC 50 or 60 Hz for 1 min between terminals with different charge Vibration resistance Malfunction 10 to 55 Hz 20 m s2 for 10 min each in X Y and Z directions Des...

Страница 6: ...ection 2 These keys are disabled when starting and stopping operation has been disabled with operation control key protection 1 Display No 1 Displays the process value PV or parameter For the E5CSL the set point or parameter setting is also displayed 2 Display No 2 Displays the set point SP or parameter setting 3 Deviation Show the relation between the process value and the set point Indicators Li...

Страница 7: ...minal Cover E53 COV19 Note The E53 COV10 cannot be used 48 48 4 8 Front Panel E53 COV20 Note 1 This Front Panel accessory is required to attach the Y92A 48B or Y92A 48D 2 This Front Panel accessory is only the frame It does not include the plastic cover Fixture Accessory 69 6 to 77 6 87 72 72 76 4 7 67 67 Y92F 45 72 x 72 48 x 48 2 7 62 8 78 87 Panel 1to8mm Mounted to E5CWL ...

Страница 8: ...ller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display 11 A switch or circuit breaker should be provided close to this unit The switch or circuit breaker should be within easy reach of the operator and must be marked as a disconnecting means for this unit 12 Do not use paint thinner or similar chemical t...

Страница 9: ...low Sections without any specification on their degree of protection or those with IP 0 are not waterproof Front panel IP50 Rear case IP20 Terminal section IP00 Operating Precautions 1 It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON Due consideration must be given to this time when incorporating Temperature Controllers in a sequence circuit 2 ...

Страница 10: ...E5CSL E5CWL 9 ...

Страница 11: ...E5CSL E5CWL 10 ...

Страница 12: ...ED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards codes or regulations that apply to the combination of products in the customer s application or use of the products Take all necessary steps to determine the suitabili...

Страница 13: ...73 5302 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Tokyo JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA CO LTD Room 2211 Bank of China Tow...

Страница 14: ...ted delivery time enquiry in real time Logistics systems for the shipment of materials almost anywhere in the world Purchasing management order record and tracking of shipments To access the product click on the green button Product Code Reference Product link Timers hard plastic protective cover 48x48 156312 Y92A 48D Buy on EAN Temperature and Process Terminals cover E5CB 353953 E53 COV19 Buy on ...

Отзывы: