5.2 Operation Level
5-5
P
a
ra
meters
ALM2 mode Alarm value 2
This parameter is set to the input values “X” or “Y” in the alarm type list.
The ALM will flash in the display while the alarm value 2 is displayed.
•
This parameter sets the alarm value for alarm output 2.
* The decimal position is set automatically by the selected Sensor.
Alarm
type
Setting range
Unit
Default
1 to 7
0 to input setting range full scale
EU
0
8
Input setting range lower-limit value to input
setting range upper-limit value
EU 0
IS mode (1) Input shift value
h
/
l
•
Sometimes an error occurs between the set point and the actual
temperature. To offset this, a compensated value can be obtained by adding
an input shift value to the input. The compensated value is displayed as the
measurement value and used for control. (This applies when input shift is
enabled.)
•
This parameter is displayed only when control mode switch 4 is ON. Even
when the switch is OFF, the input shift function remains enabled.
•
The entire input range is shifted by a fixed rate. If the input shift value is set to
−
1
°
C, control will be performed for a value 1
°
C lower than the measured
temperature.
* The set value H is a positive value, and L is a negative value.
* The decimal position is set automatically by the selected Sensor.
Setting range
Unit
Default
L99 to H99 (
−
99 to 99)
EU H0
Function
Setting
Function
Setting