![Omron E5CS-U Скачать руководство пользователя страница 103](http://html.mh-extra.com/html/omron/e5cs-u/e5cs-u_user-manual_744347103.webp)
Sensor Input Setting Range, Indication Range, Control Range
A-13
Appendices
Input type
Specifica-
tions
Temperature
range
Input temperature range
Control range
0
−
99 to 850 (
°
C)/
−
99 to 1,500 (
°
F)
−
119 to 870 (
°
C)/
−
139 to 1,540 (
°
F)
1
0.0 to 199.9 (
°
C)/0.0 to 199.9 (
°
F)
−
20.0 to 219.9 (
°
C)/
−
40.0 to 239.9 (
°
F)
2
−
99 to 99 (
°
C)/
−
99 to 99 (
°
F)
−
119 to 119 (
°
C)/
−
139 to 139 (
°
F)
3
0 to 200 (
°
C)/0 to 200 (
°
F)
−
20 to 220 (
°
C)/
−
40 to 240 (
°
F)
Pt100
4
0 to 400 (
°
C)/0 to 400 (
°
F)
−
20 to 420 (
°
C)/
−
40 to 440 (
°
F)
5
−
99 to 500 (
°
C)/
−
99 to 900 (
°
F)
−
199 to 520 (
°
C)/
−
139 to 940 (
°
F)
6
0.0 to 199.9 (
°
C)/0.0 to 199.9 (
°
F)
−
20.0 to 219.9 (
°
C)/
−
40.0 to 239.9 (
°
F)
7
−
99 to 99 (
°
C)/
−
99 to 99 (
°
F)
−
119 to 119 (
°
C)/
−
139 to 139 (
°
F)
8
0 to 200 (
°
C)/0 to 200 (
°
F)
−
20 to 220 (
°
C)/
−
40 to 240 (
°
F)
Multi-input
(thermocouple/
platinum
resistance
thermometer)
models
(control mode
switch 5: ON)
JPt100
9
0 to 400 (
°
C)/0 to 400 (
°
F)
−
20 to 420 (
°
C)/
−
40 to 440 (
°
F)
•
The default is 2 for thermocouple input, 3 for platinum resistance thermometer input, 1 for thermistor
input, and 0 for multi-input (thermocouple/platinum resistance thermometer) models.
•
The applicable standards for each of the above input ranges are as follows:
K, J, T, N, R: JIS C1602-1995, IEC 584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
JPt100: JIS C 1604-1989, JIS C 1606-1989
Pt100: JIS C 1604-1997, IEC 751
Element-compatible thermistors (6 K
Ω
(0°C)), (30 K
Ω
(0°C)), 550
Ω
(200°C)), 4 K
Ω
(200°C)):
JIS C1611-1995
•
The input indication range is the range that can be displayed for the control range (
−
99 to 1999).
*
The PV display is shown in units of 1°C/°F, but the control range is determined up to one decimal