3.9 Shifting Input Values
3-17
Basic
Oper
ations
●
Shift Method
1.
Make sure that the control target temperature (C) and Controller
temperature (B) match, with the control target temperature near
the set point.
2.
Check the control target temperature (B) and the Controller
readout (A).
Subtract the Controller readout temperature (A) from the control
target temperature (B)
Set the result as the input shift value. The shift is illustrated
below.
3.
After setting the input shift values, check the Controller readout
(A) and the control target temperature (B). If they are almost the
same, this completes shifting the temperature input.
Input Shift
Controller readout (A)
Controller readout
after shifting
(e.g., 120
°
C)
0
After shifting
Input shift value (e.g., 10
°
C)
Before shifting
Control target
temperature (B)
Near set point
(e.g., 120
°
C)
Controller readout
before
shifting
(e.g., 110
°
C)
Содержание E5CS-U