background image

E5CN-H

8

USB-Serial Conversion Cable

Note:

A driver must be installed in the personal computer. Refer to 
installation information in the operation manual for the 
Conversion Cable.

Communications Specifications

*

The baud rate, data bit length, stop bit length, and vertical parity can 
be individually set using the Communications Setting Level.

Current Transformer (Order Separately) 
Ratings

Heater Burnout Alarms, SSR Failure 
Alarms, and Heater Overcurrent Alarms

*1.

For heater burnout alarms, the heater current will be measured 
when the control output is ON, and the output assigned to the 
alarm 1 function will turn ON if the heater current is lower than the 
set value (i.e., heater burnout detection current value). 

*2.

For SSR failure alarms, the heater current will be measured when 
the control output is OFF, and the output assigned to the alarm 1 
function will turn ON if the heater current is higher than the set 
value (i.e., SSR failure detection current value).

*3.

For heater overcurrent alarms, the heater current will be 
measured when the control output is ON, and the output assigned 
to the alarm 1 function will turn ON if the heater current is higher 
than the set value (i.e., heater overcurrent detection current 
value).

Electrical Life Expectancy Curve for 
Relays (Reference Values)

Applicable OS

Windows XP/Vista/7/8

Applicable software

CX-Thermo version 4 or higher

Applicable models

E5AN/E5EN/E5CN/E5CN-U/
E5AN-H/E5EN-H/E5CN-H

USB interface standard

Conforms to USB Specification 1.1.

DTE speed

38400 bps

Connector specifications

Computer: USB (type A plug)
Temperature Controller: Setup Tool 
port (on bottom of Controller)

Power supply

Bus power (Supplied from USB 
host controller.)

Power supply voltage

5 VDC

Current consumption

70 mA

Ambient operating 
temperature

0 to 55°C (with no condensation or 
icing)

Ambient operating humidity

10% to 80%

Storage temperature

20 to 60°C (with no condensation 

or icing)

Storage humidity

10% to 80%

Altitude

2,000 m max.

Weight

Approx. 100 g

Transmission line 
connection method

RS-485: Multipoint
RS-232C: Point-to-point

Communications

RS-485 (two-wire, half duplex)/RS-232C

Synchronization 
method

Start-stop synchronization

Protocol

CompoWay/F, SYSWAY, or Modbus

Baud rate

1200, 2400, 4800, 9600, 19200, 38400, or 
57600 bps

Transmission code

ASCII (CompoWay/F, SYSWAY)
RTU (Modbus)

Data bit length 

*

7 or 8 bits

Stop bit length 

*

1 or 2 bits

Error detection

Vertical parity (none, even, odd)
Frame check sequence (FCS) with SYSWAY
Block check character (BCC) with 
CompoWay/F or CRC-16 Modbus

Flow control

None

Interface

RS-485, RS-232C

Retry function

None

Communications 
buffer

217 bytes

Communications 
response wait time

0 to 99 ms
Default: 20 ms

Dielectric strength

1,000 VAC for 1 min

Vibration resistance

50 Hz, 98 m/s

2

Weight

E54-CT1: Approx. 11.5 g, 
E54-CT3: Approx. 50 g

Accessories (E54-CT3 only)

Armatures (2)
Plugs (2)

CT input (for heater 
current detection)  

Models with detection for single-
phase heaters: One input 
Models with detection for single-
phase or three-phase heaters: Two 
inputs

Maximum heater current

50 A AC

Input current indication 
accuracy

±

5% FS 

±

1 digit max.

Heater burnout alarm 
setting range 

*

1

0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms

SSR failure alarm setting 
range 

*

2

0.1 to 49.9 A (in units of 0.1 A)
Minimum detection OFF time: 100 ms 

Heater overcurrent alarm 
setting range 

*

3

0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms 

500

300

100

50

30

10

5

3

1

0

1

2

3

4

5

6

E5C

N

-H

250 

V

AC, 30 

V

DC 

(resisti

v

e load)

cos

φ

 = 1

S

w

itching c

u

rrent (A)

Lif

e (

×

 10

4

 oper

ations)

Buy Now: www.ValinOnline.com | Phone: 800-774-5630 | Email: [email protected]

Содержание E5CN-HC2M-500

Страница 1: ...or the most recent information on models that have been certified for safety standards refer to your OMRON website Universal Sensor Inputs Universal thermocouple Pt analog current voltage inputs Indication Accuracy Thermocouple Pt input 0 1 of PV Analog input 0 1 FS 2 level Display PV and SV 5 digit Display with high resolution of 0 01 C E5CN H Event Inputs None Two Sampling Period 60 ms Control O...

Страница 2: ...r overcurrent detection CT1 HH Heater burnout SSR failure Heater overcurrent detection CT2 B Two event inputs 03 RS 485 communications H03 Heater burnout SSR failure Heater overcurrent detection CT1 RS 485 communications HB Heater burnout SSR failure Heater overcurrent detection CT1 Two event inputs HH03 Heater burnout SSR failure Heater overcurrent detection CT2 RS 485 communications H01 Heater b...

Страница 3: ...elay output E5CN HR2MD W 500 Voltage output for driving SSR E5CN HQ2MD W 500 Current output E5CN HC2MD W 500 Functions Model Communications RS 485 3 phase heater burnout SSR failure Heater overcurrent detection E53 CNHH03N2 Heater burnout SSR failure Heater overcurrent detection Event inputs E53 CNHBN2 Communications RS 485 Control output 2 Voltage for driving SSR E53 CNQ03N2 Communications RS 485...

Страница 4: ...ow Approx 7 mA per contact Logic opera tions Number of operations 8 max Combinations can be made using work bits Operations Logic operation Any of the following four patterns can be selected The input status may be inverted A and B or C and D A or C and B or D A or B or C or D A and B and C and D A B C and D are four inputs Delay ON delay or OFF delay for the results of the logic operation given a...

Страница 5: ...0 500 0 500 0 400 0 400 0 400 0 400 0 400 0 200 00 200 00 200 00 200 00 100 0 100 0 100 0 0 0 0 0 0 0 0 0 0 0 0 0 50 00 20 0 50 00 100 0 20 0 50 00 50 00 100 0 200 0 199 9 199 9 200 0 200 0 199 9 200 0 200 0 199 9 200 0 Setting number 0 1 2 24 3 4 5 6 21 7 8 22 9 10 23 11 12 13 14 15 16 17 18 19 20 25 26 27 28 29 Shaded settings are the default settings The applicable standards for the input types...

Страница 6: ...n alarm value X is negative 0 Alarm function OFF Output OFF No alarm 1 1 Upper and lower limit 2 Set the deviation in the set point by setting the alarm upper limit H and alarm lower limit L 2 Upper limit Set the upward deviation in the set point by setting the alarm value X 3 Lower limit Set the downward deviation in the set point by setting the alarm value X 4 1 Upper and lower limit range 3 Set...

Страница 7: ...roportional band P Temperature input 0 1 to 3240 0 C or F in units of 0 1 C or F Analog input 0 1 to 999 9 FS in units of 0 1 FS Integral time I 0 0 to 3240 0 s in units of 0 1 s Derivative time D 0 0 to 3240 0 s in units of 0 1 s Control period 0 5 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in units of 0 1 Alarm setting range 19999 to 32400 decimal point position depends on input t...

Страница 8: ...ge 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55 C with no condensation or icing Ambient operating humidity 10 to 80 Storage temperature 20 to 60 C with no condensation or icing Storage humidity 10 to 80 Altitude 2 000 m max Weight Approx 100 g Transmission line connection method RS 485 Multipoint RS 232C Point to point Communications RS 485 two wire half duplex RS 232C Syn...

Страница 9: ... and Transfer Output 11 12 13 14 15 EV1 EV2 Event Inputs E53 CNBN2 E53 CNQHHN2 11 12 13 14 15 CT1 Control Output 2 and CT E53 CNQHN2 E53 CN03N2 E53 CNQ03N2 E53 CNH03N2 E53 CNHH03N2 E53 CNQFN2 E53 CN01N2 E53 CNH01N2 E53 CNQ01N2 E53 CNQBN2 E53 CNHBN2 E53 CNBFN2 SD RS 232C RD SG SD RD SG RS 232C 11 12 13 14 15 Communications RS 232 SD RD SG 11 12 13 14 15 11 12 13 14 15 RS 485 Communications RS 485 a...

Страница 10: ...ofing Panel Cutout Mounted Separately Group Mounted 48 48 44 8 44 8 48 8 6 1 5 91 78 58 Terminal Cover E53 COV17 Accessory Mounting Adapter Accessory Waterproof Packing Accessory E5CN H Recommended panel thickness is 1 to 5 mm Group mounting is not possible in the vertical direction Maintain the specified mounting space between Controllers To mount the Controller so that it is waterproof insert th...

Страница 11: ...n not be used E54 CT3 Accessory Armature 30 21 15 5 8 dia 25 3 40 10 5 2 8 7 5 10 Two 3 5 dia 40 40 30 12 dia 9 2 36 dia 15 30 Two M3 depth 4 Approx 3 dia 18 22 Approx 6 dia Plug Armature Lead E54 CT1 E54 CT3 Connection Example Plug E54 CT1 Thru current Io vs Output Voltage Eo Reference Values Maximum continuous heater current 50 A 50 60 Hz Number of windings 400 2 Winding resistance 18 2 Ω Thru c...

Страница 12: ...nted to E5CN H Note 1 Use this Adapter when the panel has already been prepared for the E5B 2 The Adapter is available only in black 50 61 3 5 38 48 100 5 Y92F 52 Note This Adapter cannot be used together with the Terminal Cover Remove the Terminal Cover to use the Adapter Mounted to E5CN H Buy Now www ValinOnline com Phone 800 774 5630 Email CustomerService valin com ...

Страница 13: ...on Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity with any standards codes or regulations which apply to the combination of the Product in the Buyer s application or use of the Product At Buyer s request Omron will provide applicable third party certification documents identifying rating...

Отзывы: