E5CN-H

Characteristics

*1.

The indication accuracy of K thermocouples in the 

200 to 1300

°

C range, T and N thermocouples at a temperature of 

100

°

C max., and U 

and L thermocouples at any temperatures is 

±

2

°

±

1 digit max. The indication accuracy of the B thermocouple at a temperature of 400

°

C max. 

is not specified. The indication accuracy of B thermocouples in the 400 to 800

°

C range is 

±

3

°

C max. The indication accuracy of the R and S 

thermocouples at a temperature of 200

°

C max. is 

±

3

°

±

1 digit max. The indication accuracy of W thermocouples is 

±

0.3 of PV or 

±

3

°

C, 

whichever is greater, 

±

1 digit max. The indication accuracy of PL II thermocouples is 

±

0.3 of PV or 

±

2

°

C, whichever is greater, 

±

1 digit max.

*2.

Ambient temperature: 

10

°

C to 23

°

C to 55

°

C, Voltage range: 

15% to 10% of rated voltage

*3.

K thermocouple at 

100

°

C max.: 

±

10

°

C max.

*4.

External communications (RS-232C or RS-485) and cable communications for the Setup Tool can be used at the same time.

*5.

Refer to information on maritime standards in 

Safety Precautions for E5

@

N/E5

@

N-H

 for compliance with Lloyd's Standards. 

*6.

Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)

Indication accuracy

Thermocouple: (

±

0.1% of indicated value or 

±

1

°

C, whichever is greater) 

±

1 digit max. 

*

1

Platinum resistance thermometer: (

±

0.1% of indicated value or 

±

0.5

°

C, whichever is greater) 

±

1 digit max.

Analog input: 

±

0.1% FS 

±

1 digit max.

CT input: 

±

5% FS 

±

1 digit max.

Transfer output accuracy

±

0.3% FS max.

Influence of temperature 

*

2

Thermocouple input (R, S, B, W, PLII): (

±

1% of PV or 

±

10

°

C, whichever is greater) 

±

1 digit max.

Other thermocouple input: (

±

1% of PV or 

±

4

°

C, whichever is greater) 

±

1 digit max. 

*

3

Platinum resistance thermometer: (

±

1% of PV or 

±

2

°

C, whichever is greater) 

±

1 digit max.

Analog input: (

±

1%FS) 

±

1 digit max.

Influence of voltage 

*

2

Influence of EMS.

(at EN 61326-1)
Input sampling period

60 ms

Hysteresis

Temperature input: 0.1 to 3240.0

°

C or 

°

F (in units of 0.1

°

C or 

°

F)

Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)

Temperature input: 0.1 to 3240.0

°

C or 

°

F (in units of 0.1 

°

C or 

°

F)

Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)

Integral time (I)

0.0 to 3240.0 s (in units of 0.1 s)

Derivative time (D)

0.0 to 3240.0 s (in units of 0.1 s)

Control period

0.5, 1 to 99 s (in units of 1 s)

Manual reset value

0.0 to 100.0% (in units of 0.1%)

Alarm setting range

19999 to 32400 (decimal point position depends on input type)

Affect of signal source 

resistance

Thermocouple: 0.1

°

C/

Ω

 max. (100 

Ω

 max.)

Platinum resistance thermometer: 0.1

°

C/

Ω

 max. (10 

Ω

 max.)

Insulation resistance

20 M

Ω

 min. (at 500 VDC)

Dielectric strength

2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)

Vibration

resistance

Malfunction

10 to 55 Hz, 20 m/s

2

 for 10 min each in X, Y, and Z directions

Destruction

10 to 55 Hz, 0.75-mm single amplitude for 2 hrs each in X, Y, and Z directions

Shock 

resistance

Malfunction

100 m/s

2

, 3 times each in X, Y, and Z directions

Destruction

300 m/s

2

, 3 times each in X, Y, and Z directions

Weight

Controller: Approx. 150 g, Mounting Bracket: Approx. 10 g

Degree of protection

Front panel: IP66, Rear case: IP20, Terminals: IP00

Memory protection

Non-volatile memory (number of writes: 1,000,000 times)

Setup Tool

CX-Thermo version 4.0 or higher

Setup Tool port

Provided on the bottom of the E5CN-H. Use this port to connect a computer to the E5CN-H.

An E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN-H. 

*

4

Standards

Approved

standards

UL 61010-1, CSA C22.2 No. 1010-1

Conformed 

standards

EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards 

*

5

EMC

EMI: EN 

61326-1 

*

6

Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A

Noise Terminal Voltage: 

EN 55011 Group 1, class A

EMS: EN 

61326-1 

*

6

ESD Immunity: 

EN 61000-4-2

Electromagnetic Field Immunity: 

EN 61000-4-3

Burst Noise Immunity: 

EN 61000-4-4

Conducted Disturbance Immunity: 

EN 61000-4-6

Surge Immunity: 

EN 61000-4-5

Power Frequency Magnetic Field Immunity: 

EN 61000-4-8

Voltage Dip/Interrupting Immunity: 

EN 61000-4-11

Buy Now: www.ValinOnline.com | Phone: 800-774-5630 | Email: [email protected]

Содержание E5CN-HC2M-500

Страница 1: ...or the most recent information on models that have been certified for safety standards refer to your OMRON website Universal Sensor Inputs Universal thermocouple Pt analog current voltage inputs Indication Accuracy Thermocouple Pt input 0 1 of PV Analog input 0 1 FS 2 level Display PV and SV 5 digit Display with high resolution of 0 01 C E5CN H Event Inputs None Two Sampling Period 60 ms Control O...

Страница 2: ...r overcurrent detection CT1 HH Heater burnout SSR failure Heater overcurrent detection CT2 B Two event inputs 03 RS 485 communications H03 Heater burnout SSR failure Heater overcurrent detection CT1 RS 485 communications HB Heater burnout SSR failure Heater overcurrent detection CT1 Two event inputs HH03 Heater burnout SSR failure Heater overcurrent detection CT2 RS 485 communications H01 Heater b...

Страница 3: ...elay output E5CN HR2MD W 500 Voltage output for driving SSR E5CN HQ2MD W 500 Current output E5CN HC2MD W 500 Functions Model Communications RS 485 3 phase heater burnout SSR failure Heater overcurrent detection E53 CNHH03N2 Heater burnout SSR failure Heater overcurrent detection Event inputs E53 CNHBN2 Communications RS 485 Control output 2 Voltage for driving SSR E53 CNQ03N2 Communications RS 485...

Страница 4: ...ow Approx 7 mA per contact Logic opera tions Number of operations 8 max Combinations can be made using work bits Operations Logic operation Any of the following four patterns can be selected The input status may be inverted A and B or C and D A or C and B or D A or B or C or D A and B and C and D A B C and D are four inputs Delay ON delay or OFF delay for the results of the logic operation given a...

Страница 5: ...0 500 0 500 0 400 0 400 0 400 0 400 0 400 0 200 00 200 00 200 00 200 00 100 0 100 0 100 0 0 0 0 0 0 0 0 0 0 0 0 0 50 00 20 0 50 00 100 0 20 0 50 00 50 00 100 0 200 0 199 9 199 9 200 0 200 0 199 9 200 0 200 0 199 9 200 0 Setting number 0 1 2 24 3 4 5 6 21 7 8 22 9 10 23 11 12 13 14 15 16 17 18 19 20 25 26 27 28 29 Shaded settings are the default settings The applicable standards for the input types...

Страница 6: ...n alarm value X is negative 0 Alarm function OFF Output OFF No alarm 1 1 Upper and lower limit 2 Set the deviation in the set point by setting the alarm upper limit H and alarm lower limit L 2 Upper limit Set the upward deviation in the set point by setting the alarm value X 3 Lower limit Set the downward deviation in the set point by setting the alarm value X 4 1 Upper and lower limit range 3 Set...

Страница 7: ...roportional band P Temperature input 0 1 to 3240 0 C or F in units of 0 1 C or F Analog input 0 1 to 999 9 FS in units of 0 1 FS Integral time I 0 0 to 3240 0 s in units of 0 1 s Derivative time D 0 0 to 3240 0 s in units of 0 1 s Control period 0 5 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in units of 0 1 Alarm setting range 19999 to 32400 decimal point position depends on input t...

Страница 8: ...ge 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55 C with no condensation or icing Ambient operating humidity 10 to 80 Storage temperature 20 to 60 C with no condensation or icing Storage humidity 10 to 80 Altitude 2 000 m max Weight Approx 100 g Transmission line connection method RS 485 Multipoint RS 232C Point to point Communications RS 485 two wire half duplex RS 232C Syn...

Страница 9: ... and Transfer Output 11 12 13 14 15 EV1 EV2 Event Inputs E53 CNBN2 E53 CNQHHN2 11 12 13 14 15 CT1 Control Output 2 and CT E53 CNQHN2 E53 CN03N2 E53 CNQ03N2 E53 CNH03N2 E53 CNHH03N2 E53 CNQFN2 E53 CN01N2 E53 CNH01N2 E53 CNQ01N2 E53 CNQBN2 E53 CNHBN2 E53 CNBFN2 SD RS 232C RD SG SD RD SG RS 232C 11 12 13 14 15 Communications RS 232 SD RD SG 11 12 13 14 15 11 12 13 14 15 RS 485 Communications RS 485 a...

Страница 10: ...ofing Panel Cutout Mounted Separately Group Mounted 48 48 44 8 44 8 48 8 6 1 5 91 78 58 Terminal Cover E53 COV17 Accessory Mounting Adapter Accessory Waterproof Packing Accessory E5CN H Recommended panel thickness is 1 to 5 mm Group mounting is not possible in the vertical direction Maintain the specified mounting space between Controllers To mount the Controller so that it is waterproof insert th...

Страница 11: ...n not be used E54 CT3 Accessory Armature 30 21 15 5 8 dia 25 3 40 10 5 2 8 7 5 10 Two 3 5 dia 40 40 30 12 dia 9 2 36 dia 15 30 Two M3 depth 4 Approx 3 dia 18 22 Approx 6 dia Plug Armature Lead E54 CT1 E54 CT3 Connection Example Plug E54 CT1 Thru current Io vs Output Voltage Eo Reference Values Maximum continuous heater current 50 A 50 60 Hz Number of windings 400 2 Winding resistance 18 2 Ω Thru c...

Страница 12: ...nted to E5CN H Note 1 Use this Adapter when the panel has already been prepared for the E5B 2 The Adapter is available only in black 50 61 3 5 38 48 100 5 Y92F 52 Note This Adapter cannot be used together with the Terminal Cover Remove the Terminal Cover to use the Adapter Mounted to E5CN H Buy Now www ValinOnline com Phone 800 774 5630 Email CustomerService valin com ...

Страница 13: ...on Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity with any standards codes or regulations which apply to the combination of the Product in the Buyer s application or use of the Product At Buyer s request Omron will provide applicable third party certification documents identifying rating...

Отзывы: