E5AX-BA/BAH/E5EX-BA/A02/A03
E5AX-BA/BAH/E5EX-BA/A02/A03
8
Function Selector (SW201, FUNCTION)
The DIP switch sets the operating parameters listed in the following
table. All pins are factory-set to OFF.
ON1
3
4
5
6
7
8
2
Controllers with Memory Banks
Function
Pin
number
Pin
setting
Setting
Control mode
1
ON
ON/OFF operation
OFF
Feed-forward PID
operation
Control output
2
ON
Normal (cooling)
OFF
Reverse (heating)
Input shift
3
ON
Enabled
(see Note 2)
OFF
Disabled
SP (set point)
4
ON
Enabled
protection cancel
OFF
Disabled
Scale
5
ON
°
F
OFF
°
C
PID display
6
ON
Enabled
OFF
Disabled
Bank No.
7
ON
Terminal input
selection
OFF
Key input
Not used.
8
Leave turned OFF.
Note:
1. The set temperature value can be changed regardless
of the position of the key protection switch (SW101,
PROTECT) when pin 4 is set to the ON position.
2. The input shift function will be disabled regardless of the
pin position when an input shift value of 0 is set.
Controllers with Communications Capability
Function
Pin
number
Pin
setting
Setting
Control mode
1
ON
ON/OFF operation
OFF
Feed-forward PID
operation
Control output
2
ON
Normal (cooling)
OFF
Reverse (heating)
Input shift
3
ON
Enabled
OFF
Disabled
SP (set point)
4
ON
Enabled
protection cancel
OFF
Disabled
Scale
5
ON
°
F
OFF
°
C
PID display
6
ON
Enabled
OFF
Disabled
Not used.
7
Leave turned OFF.
Loop back test
8
ON
Test
OFF
Normal
Note:
1. The set temperature value can be changed regardless
of the position of the key protection switch (SW101,
PROTECT) when pin 4 is set to the ON position.
2. The input shift function will be disabled regardless of the
pin position when an input shift value of 0 is set.