E5AX-BA/BAH/E5EX-BA/A02/A03
E5AX-BA/BAH/E5EX-BA/A02/A03
13
Level 2
Level 2 is used both to display switch settings, to copy bank settings,
and to set the unit number and baud rate for communications. When
the Level Key is pressed for 2 seconds minimum after power appli-
cation, “
sl-l
” is displayed on the PV display. When the Level Key is
held down for another 2 seconds “
sl-l
” appears, “
o
” will be dis-
played on the PV display, and you will be in setting level 2 and can
use the features described below.
Control Output Value:
o
When the Temperature Controller enters level 2, the control output
value is displayed on the SV display in a range of 0.0% to 100%.
Bank Copy Function:
bcpy
The bank copy function makes it possible to copy the parameters
other than the main setting that have been stored in bank 0 to any
other bank(s) (banks 1 through 7), which require the following steps:
bcpy
- - -
PV
SV
Control output value
Unit number
Baud rate
Press
a
Bank copy
Press
a
Input type
Press
a
Press
a
Press
a
0
0
in-t
k ca
u-no
0
bp5
9600
al-1
- - -c
Alarm 1 mode
Press
a
al
- - -c
Alarm mode
al-2
- - -c
Alarm 2 mode
Communications
8 memory banks
Model with heater
burnout alarm
(Note)
(Note)
(Note)
Communications
8 memory banks
Press
a
Model without heater
burnout alarm
Note:
Displayed only when the alarm function is selected.
Stand-by
bcpy
- - -
Press the Level Key to select
display level 2 and press the
Display Key. Then the Control-
ler is ready to copy to bank.
Press the Up Key to start copy-
ing. “
copy
” is displayed on the
SV display while copying.
Execution
bcpy
copy
“
end
” is displayed on the SV
display when copying is com-
pleted.
Completion
bcpy
end
b
Note:
1. The parameters stored in bank 0 can be copied to banks
1 through 7.
2. When the parameters of bank 0 are copied, the old pa-
rameters of other banks are replaced with the parame-
ters of bank 0.
Input Type:
in-t
When “
in-t
” is displayed on the PV display, the present setting of
the input type selector (SW202) is displayed on the SV display. The
following table shows the messages that may be displayed:
Thermocouple Type (SW202, INPUT)
Display
Sensor
r pr
R
s pr
S
k ca
K
j ic
J
t cc
T
e cr
E
b pr
B
n
N
l ic
L
u cc
U
Platinum Resistance Thermometer Type (SW207, INPUT)
Display
Sensor
jpt
JPt100
pt
Pt100
Note:
JPt100: 100
°
C/139.16
Ω
PT100: 100
°
C/138.50
Ω