Operation
NOTICE:
Always turn off the power supply to the Temperature Controller before changing any switch settings.
Settings
1. Remove the internal mechanism from the housing. Lift the
internal mechanism while pressing the hook at the bottom of
the front panel.
Hook
Pull out the internal mechanism while
holding down the hook with your finger.
2. Connect a Control Output Unit to the vacant socket on the
printed circuit board as shown below.
Mount the Control Output Unit
with the mark facing the direction
indicated by the arrow.
Set the output selector (SW205, OUTPUT
TYPE) to PULSE when a Relay, SSR, or
Voltage Output Unit is mounted. Set the
output selector to CURRENT when a
Current Output Unit is mounted.
To remove a Control Output Unit, push it up with the tip of a flat-blade
screwdriver as shown below.
Flat-blade screwdriver
3. Six internal switches must be set on the E5EX: the function
selector, the alarm mode selectors 1 and 2, the output
selector, terminator switch, and the input type selector.
The figures show the locations of these switches and the pro-
tection switch on the internal mechanisms. The protection
switch can be used to disable key operation.
Protection switch
(SW101, PROTECT)
Terminator switch
(SW206, TERMINATOR)
Output type selector
(SW205, OUTPUT TYPE)
Alarm mode selector 2
(SW204, ALM2)
Alarm mode selector 1
(SW203, ALM1)
Function selector
(SW201, FUNCTION)
Input type selector
(SW202 or 207)
Output Selector (SW204, OUTPUT)
OFF
ON
PULSE
CURRENT
Output
Setting (factory-set to OFF)
Current
ON
Pulse
OFF