Error Messages
The Temperature Controller is provided with self-diagnostic functions, and will display an error message on the PV display when an error is
detected.
Message
Cause
Control output
Alarm output
Pulse output
Current output*
ffff
Input temperature has exceeded the upper
limit of the temperature range by more than
20
°
C
OFF during reverse
(heating) operation
ON during normal
(cooling) operation
4 mA during reverse
(heating) operation
20 mA during normal
(cooling) operation
Sends alarm signal in
accordance with the
set alarm mode.*
----
Input temperature has fallen below the lower
limit of the temperature range by more than
20
°
C.*
ON during reverse
(heating) operation
OFF during normal
(cooling) operation
20 mA during reverse
(heating) operation
4 mA during normal
(cooling) operation
Sends alarm signal in
accordance with the
set alarm mode.*
5.err3.
(flashes)
The thermocouple has burned out or
short-circuit bar has been removed. The plati-
num resistance thermometer has burned out
or A and B terminals have been short-cir-
cuited.
OFF
Approx. 1 mA
Sends alarm signal in
accordance with the
set alarm mode.
e111
(flashes)
e333
(flashes)
Memory failure (
e111
) or A/D converter failure
(
e333
) has occurred. Temperature Controller
must be repaired if recovery is not made by
turning power off once and on again.**
OFF
Approx. 1 mA
OFF
*When the temperature resistance thermometer is used, this message is displayed when the temperature has fallen below -99.9
°
C.
**E333 also appears if a PT platinum resistance thermometer is connected to E5EX thermocouple models.
Connection with G3PX Power Controller
Refer to the G3PX data sheet for the details of the G3PX Power Controller.
The following is possible by connecting the E5AX/E5BX to the G3PX:
Using the current output, more precise temperature control will be performed.
The life of the heater will be prolonged.
Connection Example:
Current Output (4 to 20 mA) Model with G3PX
Connection Example:
Current Output (4 to 20 mA) Model
with G3PX for Slope Variation
+
–
9
10
LOAD1
LOAD2
Heater
Temperature
Controller
4 to 20 mA
2
3
4
5
6
7
8
1
9
10
G3PX
DUTY
Internal slope setting
3
2
1
G32X-VR External
Slope Setting Adjustor
(3 k
Ω
)
100/110 VAC
LOAD1
LOAD2
9
10
Heater
Temperature
Controller
+
–
4 to 20 mA
2
3
4
5
6
7
8
1
9
10
G3PX
100/110 VAC