5-8
Explicit Messages Specific to DeviceNet-compatible Digital Controllers
Section 5-3
Exp
li
c
it
M
e
ssag
e
Co
m
m
u
n
icat
io
n
s
Note
The following table shows the relationship between the Instance IDs (01 to
04) and the Digital Controller channels (1 to 4).
Unit Con-
duction
Time or
Total RUN
Time Read
Read
Reads the PV for the
Unit conduction time or
total RUN time (unit: s)
of the Digital Controller
channel (see note 1)
specified by the
Instance ID (1 to 4).
0E hex
7A hex 01 to 04
hex
66 hex
4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
Monitor
Status of
Unit Con-
duction
Time or
Total RUN
Time Read
Read
Reads the monitor sta-
tus for the Unit conduc-
tion time or total RUN
time (unit: s) of the Dig-
ital Controller channel
(see note 1) specified
by the Instance ID (1 to
4).
0E hex
7A hex 01 to 04
hex
67 hex
1 byte
00 hex: Within
range
01 hex: Out of
range (moni-
tor value
exceeded)
Instance ID
Channel
Instance ID
Channel
01 (01 hex)
Channel 1
02 (02 hex)
Channel 2
03 (03 hex)
Channel 3
04 (04 hex)
Channel 4
Explicit
message
Read/
write
Function
Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
Содержание E5AR
Страница 2: ...E5AR ER Digital Controller DeviceNet Communications User s Manual Produced February 2004...
Страница 3: ...iv...
Страница 29: ...2 6 Functions Supported Only by the E5AR ER DRT Section 2 2 Operating Procedures...
Страница 43: ...3 14 How to Use the Terminals Section 3 2 Parts Installa tion and Wiring Circuit COM 12 V 4 7 K K...
Страница 79: ...6 8 Message Communications Performance Section 6 2 Communications Performance...
Страница 91: ...B 6 Mounted Objects Appendix B Appendix B...
Страница 95: ...C 4 DeviceNet Connection Hardware Appendix C Appendix C...
Страница 97: ...G 2 Glossary...
Страница 100: ...Index I 3 W wiring 3 10 precautions 3 9 write mode 4 12...
Страница 101: ...I 4 Index...