2-2
Introduction
Section 2-1
Op
eratin
g
P
ro
ced
ures
2-1
Introduction
Use the procedures in the following sections to prepare the E5AR/ER-DRT
Digital Controllers for use. Refer to the following reference pages/sections
provided for detailed information on each step.
2-1-1
Setup Procedure
2-1-2
Startup Procedure
Prepare the master, DeviceNet communications power supply, and Configura-
tor that will be used in the system. Use the Configurator to allocate Digital
Controller data in the IN and OUT Areas. Refer to the
DeviceNet Operation
Manual
(W267) for information on related connection devices.
Note
Up to 100 words each can be allocated in the IN Area and OUT Area for
remote I/O communications. To read and write larger amounts of data, use
explicit messages. Use explicit message communications also for reading and
writing data only when required.
Step
Item
Details
Reference
1
Mount the Digital Controller.
Mount the Digital Controller to the panel.
page 3-4
2
Wire the Digital Controller.
Wire the temperature inputs and control outputs to the Digital
Controller terminals.
Note
Do not turn ON the power supply to the peripheral
devices at this time.
page 3-10
3
Turn ON the power to the Digital Con-
troller.
Turn ON the power connected to the Digital Controller.
Note
The Digital Controller will start.
page 3-10
4
Set the DeviceNet node address.
Set the DeviceNet node address (0 to 63) for the Digital Con-
troller on the front panel. Set a unique node address for each
slave connected to the same master.
page 2-3
5
Turn OFF the power to the Digital
Controller.
Turn OFF the power connected to the Digital Controller.
---
Step
Item
Details
Reference
6
Connect the DeviceNet com-
munications connector.
Connect the DeviceNet communications connector.
Note
Do not turn ON the communications power supply at
this time. This power supply is also used as the inter-
nal circuit power supply for DeviceNet communica-
tions.
page 3-15
7
Turn ON the power to the Digi-
tal Controller.
Turn ON the power connected to the Digital Controller.
Note
The Digital Controller will start.
page 3-10
8
Turn ON the DeviceNet com-
munications power (V+, V
−
).
Turn ON the communications power supply to DeviceNet.
Note
The DeviceNet communications will start.
---
9
Check the MS/NS indicators
Check that the status of the MS and NS indicators is as fol-
lows:
MS: Operating normally when lit green.
NS: Operating normally when lit green.
(DeviceNet online or communications connected.)
page 3-3
Содержание E5AR
Страница 2: ...E5AR ER Digital Controller DeviceNet Communications User s Manual Produced February 2004...
Страница 3: ...iv...
Страница 29: ...2 6 Functions Supported Only by the E5AR ER DRT Section 2 2 Operating Procedures...
Страница 43: ...3 14 How to Use the Terminals Section 3 2 Parts Installa tion and Wiring Circuit COM 12 V 4 7 K K...
Страница 79: ...6 8 Message Communications Performance Section 6 2 Communications Performance...