E5
j
J
E5
j
J
8
Input type selector
(INPUT)
Alarm mode selector 2
(ALM2)
Alarm mode selector 1
(ALM1)
Function selector
(FUNCTION)
Key protection switch
(PROTECT)
E5BJ
Top View
Bottom View
Alarm mode selector 2
(ALM2)
Key protection switch
(PROTECT)
Alarm mode selector 1
(ALM1)
Input type selector
(INPUT)
Function selector
(FUNCTION)
E5EJ
Top View
Bottom View
Input Type Selector (INPUT)
This selector selects the temperature sensor to be used. It is facto-
ry-set to position 2 to designate a K-type (chromel-alumel thermo-
couple) temperature sensor. The following table lists the other pos-
sible settings for temperature sensors. Refer to temperature range
charts under
Ordering Information for further information.
Switch
tti
Temperature
d
Temperature range
S
c
setting
e pe a u e
sensor code
°
C
°
F
0, 8
JPt100
–199.9 to 650.0
–199.9 to 999.9
1, 9
Pt100
–199.9 to 650.0
–199.9 to 999.9
2
K
–200 to 1,300
–300 to 2,300
3
J
–100 to
850
–100 to 1,500
4
T
–199.9 to 400.0
–199.9 to 700.0
5
L
–100 to
850
–100 to 1500
6
U
–199.9 to 400.0
–199.9 to 700.0
7
N
–200 to 1,300
–300 to 2,300
Note:
JPt100: 139.16
Ω
at 100
°
C
Pt100: 138.50
Ω
at 100
°
C
Temperature Control in Fahrenheit
1. After setting all internal switch settings, set pin number 4 of
the function switch to ON. This pin is normally set to OFF.
2. Insert the internal mechanism into the housing and turn on the
Temperature Controller.
3.
du
will be displayed. Then press the Up Key to change the
set value display into Fahrenheit “
f
.”
4. Turn off the power 2 s after the set value display has changed
to Fahrenheit.
5. Remove the internal mechanism from the housing, set pin
number 4 of the function switch to OFF, replace it and turn on
the power.
Function Selector (FUNCTION)
1
2
3
4
O
N
ON
OFF
The DIP switch sets the operating parameters listed in the following
table. All pins are factory-set to OFF.
Function selector pin
number
1
2
3
4
Output
operation
Normal
(see note 1)
ON
---
---
---
p
Reverse (see
note 1)
OFF
---
---
---
Control
d
ON/OFF
---
ON
---
---
Co
o
mode
Advanced
PID
---
OFF
---
---
PID
tuning
mode
With
auto-tuning
(see note 2)
---
---
ON
(see
note 3)
---
With fuzzy
self-tuning
---
---
OFF
(see
note 3)
---
Level
Engineering
level
---
---
---
ON
Normal
operation
---
---
---
OFF
Factory setting
OFF
OFF
OFF
OFF
Note:
1. For heating applications, use the reverse operation
mode. For cooling applications use the normal opera-
tion mode. (In other cases, select the desired setting.)
2. To start auto-tuning, press the Level and Display Keys
simultaneously, for 1 s or longer to start auto-tuning.
During auto-tuning, the set value display flashes. (The
display will stop flashing after tuning is finished.)
3. If the control mode is ON/OFF, pin 3 can be set ON or
OFF. (Pin 3 is not important in case of ON/OFF control.)