E5
j
J
E5
j
J
Fuzzy Self-tuning
Fuzzy self-tuning is a function that enables the E5
j
J to calculate
the most suitable PID constants for the controlled object.
Features
The E5
j
J judges by itself when to perform fuzzy self-tuning.
Fuzzy Self-tuning Function
The fuzzy self-tuning function has three modes.
In SRT (step response tuning) mode, the PID constants are tuned
using a step response method at the time the set point is changed.
In DT (disturbance tuning) mode, the PID constants are amended
so that the controlled temperature will be within the target range
set in advance when there is external disturbance.
In HT (hunting tuning) mode, when hunting occurs, the PID
constants are amended to suppress the hunting.
Note:
Be sure to turn on the power supply to the load either before
or simultaneously with the start of Temperature Controller
operation.
Dead time will be measured from the time the Temperature
Controller starts operating. If a load such as a heater is
turned on after the Temperature Controller is turned on,
dead time longer than the actual value will be measured
and inappropriate PID constants will be obtained. If an ex-
tremely large amount of dead time is measured, the control
amount will be set to 0% for a short period of time before
being returned to 100%, and the constants will then be re-
tuned. Retuning is performed only for large amounts of
dead time, so be sure to follow the precaution given above
when starting operation.
Startup Conditions of SRT
SRT will start if the following conditions are satisfied simultaneously
when the E5
j
J is turned on or the set point is changed.
At the time the E5
j
J starts
operating
At the time set point is
changed
1. The set point at the time the
E5
j
J starts operating is
different from the set point
used at the time SRT was
last executed (see note).
2. The difference between the
set point and the process
value at the time the E5
j
J
starts operating is larger
than the present proportion-
al band value (P) x 1.27+4.
3. The process value at the
time the E5
j
J starts oper-
ating is smaller than the set
point in reverse operation
and larger than the set point
in normal operation.
1. The new set point is differ-
ent from the set point used
at the time SRT was last
executed (see note).
2. The set point changing
range is larger than the
present proportional band
value (P) x 1.27+4.
3. The process value is in
stable condition before the
set point is changed.
4. A larger set point value is
set in reverse operation and
a smaller set point is set in
normal operation.
Note:
The last SRT-executed set point is set to 0 before shipping
and when changing from 2-PID control to 2-PID control with
fuzzy self-tuning.
Imposition Completion Condition of Step Control Amount
In order to prevent overshooting, the step controlled amount must
be imposed continuously only while the present deviation is the
same as or greater than the value obtained from the proportional
band (P) x 1.27. The step control will not be applied when the devi-
ation becomes smaller than this value.
PID Constant Refreshing Conditions
If the step control amount is applied before the maximum tempera-
ture slope (R) is obtained, SRT will not renew any PID constant. If
the proportional band obtained from the R and L values that were
measured before the imposition had been completed is larger than
the present proportional band, the PID constants will be renewed
because the measured value is in the direction towards the suitable
proportional band value, and the set point at that time will be the
SRT-executed set point.
Temperature
Slope (R)
Completion of SRT
Stable range
Time
SP
P x 1.27
Stable Temperature Status
If the temperature is within the stable range for a certain time, it is
deemed that the temperature is stable. This time is called stability
judgement time. Like PID constants, stability judgement time is ad-
justed with fuzzy self-tuning according to the characteristics of the
object to be controlled. Fuzzy self-tuning will not be activated if the
temperature is stable because the Temperature Controller deems
that temperature control is smooth.
Shorter than the stability judgement time
Set
point
Stable
range
Stable
range
(Set to
15.0
_
C
before
shipping)
Stability judgement time
Stable
Stable
Balanced Status
If the process value is within the stable range for 60 s when there is
no output, it is deemed that the the temperature is balanced.
Startup Conditions of DT
1. DT will start if the temperature that has been stable varies due
to external disturbance and the deflection of the temperature
exceeds the stable range, and then the temperature
becomes stable, provided that the number of maximum
temperature values is less than four.
2. DT will start if the set point is changed under the condition that
SRT does not start and the temperature becomes stable,
provided that the number of maximum temperature values is
less than four.
If there are four or more maximum temperature values, HT
will start.
SP
Temperature
Extreme value 2
Set point change
Time
Extreme value 1
Содержание E5 J Series
Страница 30: ...E5jJ E5jJ ...
Страница 31: ...E5jJ E5jJ ...