Standby Sequence Reset Method
It is possible to select the restart conditions of the standby sequence
of the alarm attached with standby sequence. If this parameter is set
to 0, the standby sequence will restart when the set point, alarm val-
ue, or input shift value is changed or the moment the E5
j
J starts
operating including the moment the E5
j
J is turned on. If this pa-
rameter is set to 1, the standby sequence will restart only the mo-
ment the E5
j
J is turned on. The following timing chart is an exam-
ple of a lower limit alarm attached with standby sequence.
Standby sequence releasing point
Standby
sequence restart
Standby
sequence
releasing point
OFF point due to
alarm hysteresis
Alarm point
(Standby sequence reset method 0)
(Standby sequence reset method 1)
Alarm output
Set value
change
Alarm output
in
Ć
s
Input Shift Display
It is possible to select to display or not to display the input shift func-
tion on display level 1 with this parameter.
off
: Not displayed
on
: Displayed
SV
SV
alh1
Alarm 1 Hysteresis and
alh2
Alarm 2 Hysteresis
It is possible to adjust alarm sensitivity with both these parameters
within a range of 0.1 to 999.9. Change the alarm sensitivity of the
E5
j
J if the alarm output chatters.
ON
OFF
ON
OFF
Upper limit alarm
Hysteresis
Lower limit alarm
Hysteresis
Low
temperature
Alarm point
High
temperature
Low
temperature
Alarm point
High
temperature
The alarm output will be OFF when the process value is within the
alarm hysteresis range when the E5
j
J restarts (e.g., when the
E5
j
J is turned on).
sl
-
l
Set Point Lower Limit Value (
°
C/
°
F) and
slĆh
Set Point
Upper Limit Value (
°
C/
°
F)
It is possible to limit the set point changeable range with both these
parameters. For example, if the set point lower limit value is set to
0
°
C and the set point upper limit value is set to 400
°
C, the set point
can be changed only between 0
°
C and 400
°
C.
eu
-
2
Event Input 2 Type Selection
It is possible to select the function of event input 2. If 0 (set point val-
ue selection) is selected,
sp
-
2
and
sp
-
3
will be displayed on display
level 1 and if 1 is selected RUN/STOP will be selected. When 0 is
selected, the set point can be selected from the following.
20
19
17
EV1
EV2
COM
EV1
EV2
Set point to be selected
Open
Open
SP0
Short-circuit
Open
SP1
Open
Short-circuit
SP2
Short-circuit
Short-circuit
SP3