The errors that may occur during the program execution are shown below.
9.7.1. SendCmd Instruction Error
These error codes are generated when the SendCmd instruction ends in error.
●SendCmd i
nstruction error code [
Output_CmdErrorID
,
Output_CmdErrorIDE
x]
An error code of
ErrorID
is stored in
Output_CmdsErrorID
, and an error code of
ErrorIDEx
is
stored in
Output_CmdsErrorIDEx
.
[Output_CmdErrorID]
Value
Error description
16#0400
An input parameter for an instruction exceeded the valid range for an input
variable.
16#0406
The data position specified for an instruction exceeded the data area range.
16#0407
The results of instruction processing exceeded the data area range of the
output parameter.
16#0800
An error occurred when a FINS command was sent or received.
Detailed information is stored in
Output_CmdErrorIDEx
.
16#0801
The port is being used.
Additional Information
For details on errors, refer to
A-3 Error Code Details
of the
NJ/NX-series Instructions
Reference Manual
(Cat. No. W502).
For information on troubleshooting, refer to
9-3 Troubleshooting
of the
CJ-series Serial
Communications Units Operation Manual for NJ-series CPU Unit
(Cat. No. W494).
[Output_CmdErrorIDEx]
For information on error codes to be stored, refer to the list of expansion error code
ErrorIDEx
described in
SendCmd
in
Section 2. Instruction Descriptions
of the
NJ/NX-series
Instructions Reference Manual
(Cat. No. W502).
Содержание E5*D series
Страница 51: ...9 Program 48 2 Initialization processing ...
Страница 52: ...9 Program 49 3 CompoWay F communications processing ...
Страница 53: ...9 Program 50 4 Processing number error process ...
Страница 60: ...2013 2018 0618 0113 P E1 0 ...