![Omron DeviceNet 3G8F7-DRM21-E Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/omron/devicenet-3g8f7-drm21-e/devicenet-3g8f7-drm21-e_operation-manual_743611049.webp)
32
DeviceNet Connections
Section 2-5
(3) The wire colors are listed in the following table.
3.
Tighten the line set screws for each line in the connector. Tighten the
screws to a torque between 0.25 and 0.3 N
⋅
m.
You will not be able to tighten these screws with a normal screwdriver,
which tapers at the end. You will need a screwdriver that does not taper at
the end, such as a large precision screwdriver.
When using a Thick Cable, allow sufficient cable to ensure that the tension
of the cable does not disconnect the connector.
Note
The following diagram shows the dimensions of the OMRON
XW4Z-00C screwdriver, which is ideal for these DeviceNet connec-
tors.
4.
Align the connector to the Board’s Connector and then insert the connector
until it is securely set in place. Firmly tighten the screws at both ends of the
connector. Tighten the connector mounting screws to a torque between
0.25 and 0.3 N
⋅
m.
Color
Signal
Symbol
Black
Communications power supply (negative) V
−
Blue
Signal LOW side
CAN L
---
Shield
S
White
Signal HIGH side
CAN H
Red
Communications power supply (positive)
V+
Use a flat-blade screwdriver
that does not taper at the end.
Side
Front
0.6 mm
3.5 mm
Содержание DeviceNet 3G8F7-DRM21-E
Страница 1: ...OPERATION MANUAL Cat No W381 E1 02 3G8F7 DRM21 E DeviceNet PCI Board ...
Страница 2: ...3G8F7 DRM21 E DeviceNet PCI Board Operation Manual Revised July 2005 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 29: ...12 Preparation for Operation Section 1 8 ...
Страница 67: ...50 PC Watchdog Timer Management Function Section 3 11 ...
Страница 115: ...98 Maintenance API Functions Section 4 7 ...
Страница 131: ...114 Remote I O Communications Characteristics Section 6 1 ...
Страница 145: ...Index 128 ...
Страница 147: ...130 Revision History ...