D5C

D5C-1A

@

0 (AC Models)

Be aware that the D5C-1A

@

0 not in operation has a leakage 

current of approximately 2 mA. Especially, if the load is a relay with 
a current flow of 10 mA or less, a reset failure may result due to the 
residual voltage. Therefore, connect a bleeder resistor as shown 
below so that the residual voltage will be less than the reset voltage 
of the load.

The bleeder resistance and permissible power are obtained from 
the following formula.

R

(K

Ω

) P>

(mW)

P: W number of bleeder load (Practically, the wattage must be a few 

times larger than the obtainable value.)

I: Load current (mA)

If a DC relay or DC counter is used as a load connected through an 
electronic timer or current rectification circuit, pay the utmost 
attention so that the leakage current of the D5C AC model will not 
cause the load to malfunction.

Sensitivity Adjustment

The sensitivity of the D5C can be adjusted by turning the adjuster 
on the rear side with a flat-blade screwdriver. 

The sensitivity increases by turning the adjuster clockwise (max. 30 pF) 
and decreases by turning the adjuster counterclockwise (min. 100 pF).

Be sure to turn the adjuster with a torque of 0.08 N·m or less. If 
excessive torque is applied, the adjuster will break.

Grounding

<For DC and AC Models>

In order to maintain the operational reliability of the D5C, be sure to 
ground the blue or black wire of the power cable.
(Refer to 

“Output Circuit Diagram”

 on page 4.)

Operation may fail if the D5C is not grounded.

<DC Models>

The service power supply of the PC (Programmable Controller) is 
not available to the D5C-1D

@

0. The negative line of the service 

power supply of the PC is not grounded. Therefore, the D5C may 
not operate.
Furthermore, if the negative line of the service power supply is 
grounded, the noise resistance of the PC will drop.

<AC Models>

Provided that single-phase 200 V is supplied to the D5C-1A

@

0, if 

one phase is grounded, the power supply will be short-circuited and 
a machinery breakdown will result. Use an isolating transformer 
and ground the secondary side of the transformer instead.

In the above case, be sure to ground the secondary side, otherwise 
the D5C may not operate.

The lead wire colors of the D5C have been changed in compliance with the 
latest applicable JIS standards. Colors in parentheses are previous ones.

Others

Do not disassemble the D5C, otherwise the internal wiring will be 
damaged and the D5C will fail to operate.

The sealing of the D5C uses nitrile butadiene rubber (NBR), which 
is highly oil resistive. If exposed to some types of oil or chemical 
indoors or outdoors, however, the NBR may deteriorate. Contact 
your OMRON representative for details.

When mounting the antenna to the D5C, be sure to tighten the 
antenna to a torque of 0.39 to 0.83 N·m. If the antenna is not 
tightened securely, the built-in contact may break.

If an appropriate antenna is mounted to a free attachment model, 
hold the nut on the outer side with a wrench so that the nut will not 
move. Then tighten the nut on the inner side within a torque range 
of 0.78 and 1.18 N·m.

AC power
supply Vs

Bleeder resistor R

Load

Vs

10

I

Vs

2

R

SENSI

Set point

D5C

AC

Brown
(White)

Blue
(Black)

Load

Wrench

Direction
of turn

Antenna

Содержание D5C Series

Страница 1: ...ting Free attachment to enable changing the antenna shape according to the application Malfunction may occur if used in locations subject to water or oil Be sure to read Safety Precautions on page 6 t...

Страница 2: ...0 Hz Sensitivity setting range 30 to 100 pF Current consumption 17 mA max Leakage current Circuit 2 mA max Antenna 1 mA max 1 mA max Response time 2 ms max 8 ms max Output current 200 mA max resistive...

Страница 3: ...ity Temperature C Sensitivity pF 10 20 30 200 150 100 50 0 With sensitivity adjuster set to minimum sensitivity With sensitivity adjuster set to maximum sensitivity Voltage V Sensitivity pF 200 300 10...

Страница 4: ...ction However limit the overtravel to within 20 mm from the free position The force that pushes the actuator must not exceed 1 96 N 2 Vinyl insulated round cable oil and shock resistant type 4 dia thr...

Страница 5: ...6 N 2 Vinyl insulated round cable oil and shock resistant type 4 dia three conductors 0 3 mm2 3 Use after removing the caution label Coil Spring D5C 1AS0 2 1 LED Operation indicator M18 1 Two internal...

Страница 6: ...nded provided that the total length of the antenna is 1 m maximum Fig 2 and that the bottom of the antenna is at least 10 cm Fig 3 away from the ground Refer to the illustrations below The D5C may be...

Страница 7: ...er supply of the PC Programmable Controller is not available to the D5C 1D 0 The negative line of the service power supply of the PC is not grounded Therefore the D5C may not operate Furthermore if th...

Страница 8: ...products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control systems combustion systems r...

Отзывы: