background image

 

 

OMRON ELECTRONICS LTD 

 Technical Support: 0870 752 0871 or visit www.myOMRON.com 

28

 

 

 
Click 

Yes

 again… 

 

 

 
It will take no more than about 5 seconds to download the entire PLC application.  Upon 
completion, click 

OK

… 

 

 

 
If you see this message below, click 

Yes

 to return the PLC to Monitormode (Run). 

If this is the first time you have used this PLC, at this point you will have to remove the 
power to it, then re-power.  With either of the above, the PLC’s POWER and RUN LED 
indicators should both be lit green. 
 

 

 
 
Now follow the next steps to download the application to the NQ3 HMI… 
 
 

Содержание CP1L-E

Страница 1: ...Scope of Kits Each kit contains an NB series colour touchscreen HMI which is connected to the CP1L E PLC via the Westermo 5 port Ethernet switch using the supplied CAT6 patch cable CX Programmer V8 2...

Страница 2: ...OMRON ELECTRONICS LTD Technical Support 0870 752 0871 or visit www myOMRON com 2...

Страница 3: ...WG wire connect the V output terminal of the S8VS 06024 power supply to the input terminal of the PLC and the 24V terminal of the NB series HMI 3 Using 0 5mm2 20AWG wire connect a jumper between the t...

Страница 4: ...ELECTRONICS LTD Technical Support 0870 752 0871 or visit www myOMRON com 4 L N E 230VAC MAINS SUPPLY 0V 24V 24V 0V 24V 0V 0V for NPN 24V for PNP NQ CN222 NQ3 TQ HMI Rear CP1L M30 PLC S8VS 06024 Power...

Страница 5: ...are required Before wiring the JX inverter please refer to the Precautions for Safe Use section pages 5 9 of the User s Manual ref I558 E2 02 see Resource CD TECHNICAL DOCUMENTATION JX INVERTER It is...

Страница 6: ...front of the JX and the screw terminals of the CP1W CIF11 RS422 485 communications option module fitted in the right hand slot of the CP1L PLC 1 Insert the RJ45 connector end into the front of the JX...

Страница 7: ...rom their defaults Please refer to section 3 4 Operating Procedure of User s Manual I558 E2 02 if you are unfamiliar with the operation of the front panel keypad see Resource CD TECHNICAL DOCUMENTATIO...

Страница 8: ...m 8 6 Loosen the screw in the bottom left corner of the inverter and remove the front cover 7 Turn DIP switch S7 to the upper 485 position as indicated in the diagram below leave switch S8 in its defa...

Страница 9: ...ter please refer to the Precautions for Safe Use section of the User s Manual ref I570 E2 01 see Resource CD TECHNICAL DOCUMENTATION MX2 INVERTER It is not necessary to connect a motor to the MX2 inve...

Страница 10: ...N Neutral screw terminals of the MX2 inverter as shown in the diagram on the previous page The Earth wire is terminated into an eyelet which should be attached to the leftmost M4 chassis ground screw...

Страница 11: ...ct the black wire to the first screw terminal of the CP1W CIF11 module marked RDA and the red wire to the second screw terminal marked RDB 2 At the MX2 end connect the black wire to the terminal marke...

Страница 12: ...ld below must be changed Please be sure to reboot the power to the inverter after changing these parameters in order for the new settings to take effect The sample software application included on the...

Страница 13: ...the right most DIP switch to the ON position defines that output terminal 11 is to be used as an external safety monitor EDM output The wiring diagram on the following page assumes that a single 2 x N...

Страница 14: ...switch open the MX2 will run as normal As soon as the E stop button is pressed the MX2 s power outputs to the motor are instantly cut Please bear in mind that depending on the application this may cau...

Страница 15: ...amplifier should be attached to this filter using the supplied M4 screws 1 Connect a 230VAC supply to the filter as shown in the diagram above ensuring that an earth connection is made to the M4 stud...

Страница 16: ...of the servo amplifier and the short flying cable at the rear of the servomotor 4 Attach the motor power cable R88A CAB001 5SR E between terminal CNB of the servo amplifier and the short flying cable...

Страница 17: ...resistors in series with the CW and CCW connections Please refer to the diagram overleaf for full wiring details 1 Cut back about 25cm of the outer sheathing and braiding from the R7A CPB001S control...

Страница 18: ...he ERROR COUNTER RESET signal which resets the drive s internal following error counter in the event of a fault caused by this 10 Connect the ORANGE 1 BLACK BAND wire to output 100 06 this is the RUN...

Страница 19: ...OMRON ELECTRONICS LTD Technical Support 0870 752 0871 or visit www myOMRON com 19 SmartStep2 servo amplifier to PLC wiring PNP CONFIGURATION FOR CP1L M30DT1 D MODEL...

Страница 20: ...indicates that the system is in error 6 Connect the PINK 1 BLACK BAND wire to input 1 05 this is the IN POSITION signal which indicates that the drive has completed its move successfully 7 Cut the GR...

Страница 21: ...OMRON ELECTRONICS LTD Technical Support 0870 752 0871 or visit www myOMRON com 21 SmartStep2 servo amplifier to PLC wiring NPN CONFIGURATION FOR CP1L M30DT D MODEL...

Страница 22: ...OMRON ELECTRONICS LTD Technical Support 0870 752 0871 or visit www myOMRON com 22 SmartStep2 servo amplifier to PLC wiring PNP CONFIGURATION FOR CP1L EM30DT1 D MODEL...

Страница 23: ...er inserting the DVD Please follow the on screen instructions ensuring that you select the Complete installation option and use the 16 digit license code which came with your package Once installation...

Страница 24: ...on Kit see Resource CD SOFTWARE NQ DESIGNER or can be freely downloaded via www myOMRON com You will need to create a simple user account requiring just an e mail address and a password then go to Dow...

Страница 25: ...he SOFTWARE folder on the Resource CD CP1L PLC DEMO LeanKitDemoCP1L sub folder and select the LeanKitDemoSoftware cxp file and click Open Connect the USB programming cable CP1W CN221 between your PC s...

Страница 26: ...port 0870 752 0871 or visit www myOMRON com 26 Windows will then install the USB driver for the PLC If you see the screen below which depends upon your version of Windows click Continue Anyway Click F...

Страница 27: ...small yellow triangle symbol on the top icon bar turns from grey to yellow as shown circled in red below This is the Work Online shortcut also available from the PLC menu Clicking on this connects CX...

Страница 28: ...Upon completion click OK If you see this message below click Yes to return the PLC to Monitormode Run If this is the first time you have used this PLC at this point you will have to remove the power...

Страница 29: ...t and the NQ3 HMI s SLAVE port at the rear of the unit If this is the first time you have connected an NQ HMI Windows will display Found New Hardware HMI USB Device Select the Install from a specific...

Страница 30: ...progress of the download When the bargraph reaches 100 and Download Completed is displayed as per the picture above click Close At this point the NQ3 HMI will reboot and providing that the PLC softwar...

Страница 31: ...ill see the welcome screen below The HMI s system beeper can be disabled by pressing the speaker symbol in the bottom left corner Press START You will need to define your choice of connected hardware...

Страница 32: ...maximum value of 400 00Hz is possible via settings in the drive the HMI limits the input value to 50 00Hz START FWD and START REV will cause the motor to accelerate to the input frequency in a clockwi...

Страница 33: ...cal Support 0870 752 0871 or visit www myOMRON com 33 Note that AT ZERO SPEED and UNDER VOLTAGE DETECT are only available for the MX2 model Pressing the blue info symbol on the main control screen bri...

Страница 34: ...system you will be able to control it using high speed digital pulses from the PLC Pressing the SMARTSTEP2 SERVO button from the MAIN MENU screen brings up the following sub menu for servo control Th...

Страница 35: ...system will be tuned to the application by using the Auto Tune facility within CX Drive software to increase the rigidity In order to use absolute positioning and origin search must be performed to gi...

Страница 36: ...otate in the chosen direction for as long as you keep your finger on the button The PULSING indicator will light green to indicate that the PLC is outputting pulses and the IN POSN indicator will exti...

Страница 37: ...xactly one revolution At the default speed of 5 000Hz a single revolution will be completed on 0 5s The relative position value can be set between 0 100 000 pulses 40 revolutions The pulse output spee...

Страница 38: ...ing relative positioning you rotated the motor 20 turns clockwise 4 turns counter clockwise then jogged it a quarter turn counter clockwise performing an Absolute Position movement to 0 would cause th...

Страница 39: ...The CD supplied with the Lean Kit contains the demonstration software for PLC and HMI a copy of NQ Designer programming software brochures and datasheets and technical documentation User Manuals Prog...

Страница 40: ...Support 0870 752 0871 or visit www myOMRON com 40 JX MX2 INVERTER REFRESH FUNCTION BLOCK PNSPO An introduction to the JX MX2 Inverter Refresh Function Block Controlling up to 31 Inverters using MODBUS...

Страница 41: ...rters in any combination via a 2 wire RS485 network No additional programming required other than defining which nodes are present and which type of inverter JX or MX2 is used at each node JX MX2 INVE...

Страница 42: ...used D1002 1003 32 bits If bit 01 of word D1002 is set to ON and all others OFF this would mean that we have only one inverter present as Node 01 This could be done as a series of touchswitches on an...

Страница 43: ...1001 32 bits If bit 01 of word D1000 is set to ON this would mean that we have an MX2 present as Node 01 If it is OFF this means it s a JX These are only effective if the node is defined as being pre...

Страница 44: ...and and status data for each drive the I F or Interface area In our program 82 means use DM area and 100 means start at DM100 JX MX2 INVERTER REFRESH FUNCTION BLOCK PNSPO DM100 DM101 DM102 DM103 DM104...

Страница 45: ...OMRON ELECTRONICS LTD Technical Support 0870 752 0871 or visit www myOMRON com 45 CONTROLLING SMARTSTEP2 WITH CP1 PLC PNSPO Using just three instructions for complete control of the SMARTSTEP2 servo...

Страница 46: ...s encoder Z pulse and a physical limit or proxi switch on the mechanical system The method of origin search is simply defined within the PLC s settings JOGGING THE SMARTSTEP2 PNSPO The SPED instructio...

Страница 47: ...ING WITH PLS2 PNSPO The PLS2 instruction sends a number of pulses from a transistor output at a set frequency This instruction also defines the accel and decel rates of the movement profile The specif...

Страница 48: ...will move the specified distance clockwise or counter clockwise with respect to its current position Positive over travel POT and negative over travel NOT inputs from switches sensors at the physical...

Страница 49: ...ove the specified distance clockwise or counter clockwise with respect to its origin position as a number of pulses from the origin If no ORG has been performed or the power to the system has been int...

Отзывы: