9-51
9 Troubleshooting and Maintenance
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
9-4 Even
t L
ogs
9
9-4-3 Error De
scr
iptio
ns
Event name
Master Fixed Allocation Area Setting Failed
Event code
7461 0000 hex
Meaning
An error occurred in one of the following operations for fixed allocation of the master.
•
Fixed Allocation Area Setting 1 Switch (device variable
*_Sw1MstrFixAloc1Cmd
)
•
Fixed Allocation Area Setting 2 Switch (device variable
*_Sw1MstrFixAloc2Cmd
)
•
Fixed Allocation Area Setting 3 Switch (device variable *_
Sw1MstrFixAloc3Cmd
)
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At user operation
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The master function is not enabled.
Enable the master function.
Enable the master function.
The scan list is not disabled.
Disable the scan list.
Disable the scan list.
CPU Unit is not in PROGRAM mode.
Change the CPU Unit to PROGRAM
mode.
Change the CPU Unit to PROGRAM
mode.
More than one software switch
changed to TRUE at the same time.
Or, another software switch changed
to TRUE before processing was com-
pleted for a previous software switch.
Execute the software switch opera-
tions one at a time.
Execute the software switch opera-
tions one at a time.
Attached
information
None
Precautions/
Remarks
None
Содержание CJ1W-DRM21
Страница 12: ...Manual Structure 10 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 42: ...Revision History 40 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 214: ...6 Message Communications 6 26 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 345: ...Index 1 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 I Index ...
Страница 349: ......