4 Remote I/O Master Communications
4-4
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
z
With CX-Integrator
When using the CX-Integrator, you can allocate four blocks to each slave: Output (OUT) blocks 1
and 2 and input blocks 1 and 2. Each block is a maximum of 500 words. To access the allocated
area from the user program, a user-defined variable that specifies the AT specification of that area
needs to be defined.
You can use any order for block allocations and for slave allocations within each block. Each address
is allocated at least one byte (rightmost).
•
More than one word is allocated for each slave with more than16 I/O points (using it's node
address).
•
The leftmost or rightmost byte of the word is allocated to each slave that has 8 I/O points or
less.
z
Using "*_MstrAlocTblCfg[0 to 5]" (Master User-set Allocations Setup Table)
In
*_MstrAlocTblCfg[0 to 5]
(Master User-set Allocations Setup Table), set the areas and first words
for the output block (OUT 1) and the input block (IN 1) and set the area and first word for the Alloca-
tion Size Setup Table. You can allocate each slave two blocks, OUT 1 and IN 1, according to the set-
tings in this device variable for CJ-series Unit. The OUT and IN blocks will be allocated in order of
slave node addresses. Each block is a maximum of 500 words.
To access the allocated area from the user program, a user-defined variable that specifies the AT
specification of that area needs to be defined.
Each address is allocated at least one byte (rightmost).
•
More than one word is allocated for each slave with more than16 I/O points (according to its
node address).
•
The rightmost byte of the word is allocated to each slave that has 8 I/O points or less.
CJ-Series Unit memory
CPU Unit
User program
OUT
block 1
User-defined
variable
User-defined
variable
Address
Address
To Slaves
Any address order
You can set the position of each block.
An order (such as IN block 1, OUT block 2,
IN block 2 and OUT block 1) can also be used.
OUT
block 2
Address
Address
Any address order
Output area
IN
block 1
Address
Address
From Slaves
Any address order
IN
block 2
Address
Address
Any address order
Input area
CPU Unit
User program
OUT
block 1
User-defined variable
User-defined variable
Specify the area, first word, and allocation
size to allocate output/input block 1.
Device variables for CJ-series Unit
IN
block 1
Address
Address
Address
Address
To Slaves
From Slaves
Ascending order that start from address 0
CJ Unit memory
Ascending order that start from address 0
Содержание CJ1W-DRM21
Страница 12: ...Manual Structure 10 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 42: ...Revision History 40 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 214: ...6 Message Communications 6 26 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 345: ...Index 1 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 I Index ...
Страница 349: ......