Be sure to set the correct values for the Loop 1 and Loop 2 SP.
The SV value is #0000 (0
°
C) if no data is set. If the executed bank number is set
to a value out of the range from 1 to 8 the bank number reverts to the previous
value (default value = 1).
Reading Monitored Data
Read monitored data into the program using Wd (n+3) to (n+9).
4-3-2 Example 1: Write with SW2-1 in the Normal Position
Description and Conditions
Example
The user program makes the following settings:
Loop 1 SP = 200
°
C (Bank no. = 1)
Loop 2 SP = 250
°
C (Bank no. = 2)
Loop 1 executed bank number = 1
Loop 2 executed bank number = 2
Loop 1 heater burnout current value = 2.0 A
Loop 2 heater burnout current value = 2.5 A
Conditions C200H-TV001 (thermocouple)
SW203 set to 2 (K).
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
Programming
Section 4-3